Specifications of CS1D-BC042D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
CS1W-OC201 Contact Output Unit (8 points)
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
Specifications of Basic I/O Units and High-density I/O Units
Max. Switching Capacity
Min. Switching Capacity
Relay replacement
Service Life of Relay
ON Response Time
OFF Response Time
No. of Circuits
Number of Inputs ON Simulta-
neously
Surge Protector
Fuses
Insulation Resistance
Dielectric Strength
Internal Current Consumption 100 mA 5 V DC max. 48 mA 26 V DC (6 mA
Weight
Circuit Configuration
Terminal Connections
2 A 250 V AC (cos = 1), 2 A 24 V DC (16 A/Unit), 0.1 A 120 V DC
1 mA 5 V DC
NY-24W-K-IE (Fujitsu Takamizawa Component Ltd.)
Relays cannot be replaced by users.
Electrical: 150,000 operations (resistive load)/100,000 operations (inductive load)
Mechanical: 20,000,000 operations
Service life will vary depending on the connected load. Refer to page 497 for information
on service life according to the load.
15 ms max.
15 ms max.
8 independent contacts
8
None
None
20 M between external terminals and the GR terminal (500 V DC)
2,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage
current of 10 mA max.
260 g max.
2 A 250 VAC,
2 A 24 VDC,
0.1 A 120 VDC max.
Output indicator
*
NC
NC
c0
c1
c2
c3
c4
c5
c6
c7
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
OUT
OUTc
B0
B1
B2
B3
B4
B5
B6
B7
B8
B9
0
1
2
3
4
5
6
7
NC
NC
L
L
L
L
L
L
L
L
No. points ON)
* A relay contact is used,
so there is no polarity
when a DC power supply