Error Processing
10-2-8 Memory Error Check
412
It's possible that noise or
other temporary factory
caused the error. Check
the operating environment
if necessary.
Turn ON the power
supply.
Memory error occurred.
Battery connected?
backup (with BKUP
memory error)
turned OFF during
(autotransfer at
A40310 (flash
startup error)
Operation
A40309
normal?
ON?
Power
ON?
lit)?
OFF
OFF
No
Yes
Yes
No
Yes
No
ON
ON
Battery-free
necessary?
operation
No
Yes
There may be a hardware error in
internal memory. Replace the CPU
Unit.
Conditions have not been met for
automatic transfer at startup. Confirm
that the required files are on the
Memory Card and the pin 2 on the
DIP switch is OFF.
The write life of the flash memory has
been exceeded. Replace the CPU Unit.
Check to see if battery-free operation has
been set correctly. Retransfer the user
program and parameters and set the PLC
Setup so that battery errors are not
detected.
Mount a Battery.
If power was turned OFF during the
backup operation, retransfer the user
program and parameters.
Section 10-2