CS1D-BC042D Omron, CS1D-BC042D Datasheet - Page 321

no-image

CS1D-BC042D

Manufacturer Part Number
CS1D-BC042D
Description
CS1D Dual CPU Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-BC042D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
File Memory Information
286
Auxiliary Area
Battery Error Flag
(Non-fatal error)
Right CPU Unit Battery Error
Flag (Duplex CPU Systems
only)
Left CPU Unit Battery Error
Flag (Duplex CPU Systems
only)
Memory Card Type
EM File Memory Format Error
Flag
Memory Card Format Error
Flag
File Transfer Error Flag
File Write Error Flag
File Read Error
File Missing Flag
File Memory Operation Flag
Battery Errors
File Memory Information for Active CPU Unit or CPU Unit in Single CPU System
Name
Name
A40204
A32411
A32413
A34300 to
A34302
A34306
A34307
A34308
A34309
A34310
A34311
A34313
Address
Address
The following words and bits provide file memory status for Single CPU Sys-
tems or for the active CPU Unit in a Duplex CPU Systems. For a Only the
Memory Card in the active CPU Unit is accessed. For information on the CPU
Unit’s file memory-related status, refer to Read-only Words in Appendix B
Auxiliary Area Allocations.
ON if the CPU Unit’s battery is disconnected or its voltage is
low and the PLC Setup has been set to detect this error.
(Detect Low Battery)
ON if A40204 is ON in the right CPU Unit.
ON if A40204 is ON in the left CPU Unit.
The Memory Card type is output to A34300 to A34302.
(0 hex: No Memory Card; 4 hex: Flash ROM)
With a Duplex CPU System, the information depends on the
setting of duplex operation for the Memory Card, as shown
below.
• Memory Card duplex operation disabled: Memory Card
• Memory Card duplex operation enabled: Memory Card
Turns ON when a format error occurs in the first EM bank
allocated for file memory in the CPU Unit.
Turns OFF when formatting is completed normally.
ON when the Memory Card is not formatted or a formatting
error has occurred in the active CPU Unit.
ON when an error occurred while writing data to file memory
in the active CPU Unit.
ON when data cannot be written to file memory because it is
write-protected or the data exceeds the capacity of the file
memory in the active CPU Unit.
ON when a file could not be read because of a malfunction
(file is damaged or data is corrupted) in the active CPU Unit.
ON when an attempt is made to read a file that doesn’t exist
or an attempt is made to write to a file in a directory that
doesn’t exist in the active CPU Unit.
ON while any of the following operations is being executed in
the active CPU Unit. OFF when none of them are being exe-
cuted.
CMND instruction sending a FINS command to the local
CPU Unit.
FREAD/FWRIT instructions.
Program replacement using the control bit in the Auxiliary
Area.
Simple backup operation.
type for active CPU Unit is stored.
type is stored only when mounted in both CPU Units.
Description
Description
Section 8-11
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Access
Access