7-6 Editing Master Unit Parameters
7-6-3 Editing the Software Setting Table
7-6-3
7-26
Editing the Software Setting Table
Area
Word OUT
Word IN
Bit OUT
Bit IN
Participation/Communications
Error Flags: Word Units
Participation/Communications
Error Flags: Bit Units
The CompoNet Master Unit has 5 communications modes. When using
communications modes 0 to 3, the CompoNet Unit IN/OUT information is allocated
in the Special I/O Unit Area. When using communications mode 8 (Software Setting
Mode), the CompoNet Unit IN/OUT information can be allocated in the CIO, DM,
WR, and HR Areas, in addition to the Special I/O Unit Area.
The Software Setting Table is used in the following situations.
• When allocating words in an area other than the Special I/O Unit Area to Slave
• When setting the number of words allocated, e.g., when words after those
In the Software Setting Mode, memory is allocated to each Word Unit and Bit Unit
for the Word IN/OUT Areas, Bit IN/OUT Areas, Participation Flags, and
Communications Error Flags.
1. Set the communications mode to No. 8 (see note) by using the rotary switch on
Note: The Software Setting cannot be set in any communications mode other than No. 8.
2. Turn ON the CompoNet Unit and computer.
3. Start the CX-Integrator, create the I/O tables, and then connect online to the
4. Right-click the Master Unit Icon in the Network Configuration Window and
Units
allocated to the Slave Units will be used for another purpose.
CX-Integrator
the front of the Master Unit.
CompoNet Network.
select Parameter - Edit. The Master Unit’s Parameter Dialog Box will be
displayed.
Software Setting Table
Start
area/address
Mode No. = 8
Number
of nodes
CompoNet Master Unit
CS/CJ-series PLC
Word Slaves
CompoNet
User-set location→
User-set location→
User-set location→
User-set location→
User-set location→
User-set location→
The addresses and areas for the Word OUT
Area, Word IN Area, Bit OUT Area, Bit IN Area,
Participation Flags, and Communications Error
Flags are set for each Word Unit and Bit Unit.
Bit Slaves
I/O memory
Word IN Area
Word OUT Area
Word Unit Participation
Status
Bit IN Area
Bit OUT area
Bit Participation Status
:
: