3-2-10 Transferring Routing Tables to a Network PLC through a Direct Serial Connection
3. The PLC Routing Table Window will be displayed in the Main View format.
4. Select File – Open Local Routing Table File to read the saved FINS local routing
5. Select Options – Switching the target PLC, or click the
6. The Switching the target PLC Dialog Box will be displayed.
Set the following items, and switch the target PLC.
Select either of the following options.
Connect directly to the PLC using serial cable.
Connect to the PLC on the network
• Unit
• Node Address
table file.
Select the Communications Unit that connects to the network containing the
PLC that is the destination of the routing table transfer.
Select the node address to which the routing parameters are transferred.
Set the node address based on the type of network, as follows.
Select this option when switching to the PLC that is directly connected by a
serial connection. In this case, the Unit and Node Address Fields in the lower
half of the dialog box are disabled.
Select this option when switching to another PLC in the same network as the
directly connected PLC.
3-2 Setting the Routing Tables
Icon in the toolbar.
3-29