Using Parameter Edit Window
Note
Component - Parameter - Edit - Upload Button
•When parameters are uploaded from the Network Configuration Window, an asterisk
•The uploaded parameters will be discarded if the No Button is clicked to quit the Edit
1. Select the device or devices in the Network Configuration Window. (More than one
2. Select Component - Parameter - Upload.
3. Click the Yes Button.
To upload the parameters through the Edit Device Parameters Window, use the
following procedure.
1. Select the device from the Network Configuration Window.
2. Select Component - Parameter - Edit.
3. Click the Upload Button.
The following confirmation dialog box will be displayed.
4. Click the Yes Button.
Device Parameters Dialog Box after the parameters have been uploaded.
may be display to the lower left of some devices. This indicates that the I/O size of the
device is not consistent with the I/O size in the scan list in the Master Unit. Either
select View - Property, click the I/O Information Tab, click the Edit Button, and
correct the I/O size, or click the Get from Scan List Button and correct the I/O size. If
the I/O size registered in the scan list is incorrect, correct the I/O size for the device in
the Edit Device Parameter Dialog Box.
device can be selected by holding down the Ctrl Key while clicking the devices.)
The following confirmation dialog box will be displayed.
The progress window will be displayed and the parameters will be uploaded.
The progress dialog box will be displayed and the parameters will be uploaded.
6-13 Uploading and Verifying Device Parameters