Manually Setting Data Links
Procedure Using Setup Example
Setting Node Address 02
Setting Node Address 03 (Setting an Offset)
Node address 02 is set in the same way as node address 01.
For node address 03, the procedure for setting the node refresh sequence and the
offset is as follows:
1 Select node address 03 from the node address list on the left.
2 With node address 03, the node refresh sequence does not match the default, so
3 Double-click on the Offset cell, and input the data size to be offset. In this example,
Receive area from remote nodes
the order of addresses must be changed. Change the node refresh sequence by
either clicking F4: Move Up Area or F5: Move Down Area in the Function Bar, or
pressing the F4 or F5 function keys.
set the offset size to 10 words.
With this setting, 20 words sent from node 01 will be received, starting from CIO
1000, and with an offset of 10 words (i.e., CIO 1010 to CIO 1030).