6-3
114
Error Messages and Alarm Outputs
Startup
errors
Run-
ning er-
rors
SPL
Status
Startup
errors
Error Messages and Alarm Outputs
DPL
Waiting for
START
INPUT
No
SYSMAC
BUS
terminator
CPU Bus
Unit
initialization
I/O verify
error (PC
Setup)
Duplication
bus error
(power ON)
Duplication
verification
error
(power ON)
Error
CPU
WAITING
CPU
WAITING
CPU
WAITING
CPU
WAITING
CPU
WAITING
CPU
WAITING
vice error
Program-
ming De
ming De-
message
A30600
A30602
A30603
A30601
A40209
A30604
A30605
Error
flags
Auxiliary Area data
---
---
---
00E7
---
---
Error
code
A397
---
---
---
---
---
Error data
START INPUT of
CPU Rack Power
Supply Unit is
OFF.
Terminator is not
set.
Terminator of
SYSMAC BUS/2
is missing, or
CPU Bus Unit is
still initializing.
I/O Unit has been
removed.
An error was
detected in the
redundant
system’s
synchronous
transfer bus.
The ACT/STB
memory contents
(user program,
Expansion DM)
contents do not
match the
Expansion DM
size.
Cause
Connect a short-circuit so
that the START INPUT for
the Power Supply Unit on
the CPU Rack will enter.
Turn on the power to the
Remote I/O Slave Unit.
Specify the Unit connected
last as the terminator or
wait until CPU Bus Units
complete initialization.
Turn on the power to the
Remote I/O Slave Unit.
Specify the Unit connected
last as the terminator.
Verify the I/O table.
Correct the table if
necessary by create a new
one.
Turn the power OFF and
then ON again.
If the error is not corrected,
replace the Duplex Unit or
the Backplane.
Check/correct the
program. Correctly mount
the EM Unit.
Corrective action
Section
6-3