5-1
5-2
96
Inspections
1
2
3
4
5
6
Power supply
Environmental
conditions
co d o s
I/O power supply
Installation status
Unit condition
Product service life
Inspection item
Consumable Parts
Inspections
Determine whether the voltage
fluctuation is within the standard
at the power supply terminal.
Is the ambient temperature inside
the panel appropriate?
Is the ambient humidity inside the
panel appropriate?
Has dirt or dust collected?
Is the voltage fluctuation
measured at the I/O terminal
within the standard range?
Are all units securely installed?
Are all connection cables and
connectors inserted completely
and locked?
Are any of the external wiring
screws loose?
Are any of the external wiring
cables frayed?
Power Supply Unit
CPU Unit
Output Unit (Relay)
CPU Unit battery
Note Always keep spare items on hand so that they can be used as immediate repla-
It is recommended that a spare Unit always be kept on hand to ensure continued
smooth operations in case a Unit should need to be replaced. In addition, the
following consumable parts should always be kept available.
• Backup battery for CPU Unit: C500-BAT08
• Fuses for Output Units
• Output relays for Contact-type Output Units
cements.
The main components of a SYSMAC PC are semiconductors, and there are few
consumable parts. Environmental conditions, however, can lead to electrical
element deterioration, so regular inspections are required.
The standard period for inspections is six months to one year, but more frequent
inspections may be required depending on the operating environment.
Be sure to have a replacement battery ready before the currently installed bat-
tery reaches the end of its service life.
Details
100 VAC (85 to 132 VAC)
200 VAC (170 to 264 VAC)
0 to 55
10% to 90% RH with no
condensation
None
Must conform to the specifications
for individual Units.
Nothing is loose
Nothing is loose
Nothing is loose
No external abnormalities
POWER indicator must be lit on
both Units.
POWER indicator must be lit on
both Units.
The ERR indicator must not be lit.
Electrical:
Resistance load: 300,000
operations
Inductive load: 100,000
operations
Mechanical: 5,000,000 operations
_
C
Criteria
Tester
Thermometer
Hydroscope
Visual inspection
Tester
Tighten with
screwdriver.
Visual inspection
Visual inspection
---
---
g
Section
Remarks
d i
5-2