8-3 Data Read with Data Transfer Bit
CJ Position Control Units OPERATION MANUAL (CJ1W-NC214/234/414/434)
Reading Procedures
Words
PCU Control Output Memory Area
n+1
n+2
n
This section explains the procedures for and the program example of reading data from the
PCU by using the Data Read Memory area (n word, bit 13) of the PCU Control Memory area.
This section explains the procedures for reading data from the PCU with task 1 memory
operation data as an example.
Use the Special I/O Unit Memory area to read data with the data transfer bit.
You can determine the Special I/O Unit Memory area by the formula below:
Beginning word in Special I/O Unit Memory area (n) n = 2,000 + 10 × unit number
The Memory areas that are necessary for transfer are as listed below.
Always transfer in units of data when you read the data, and do not start or end in the middle of
data.
Precautions for Correct Use
PCU Control
Command
Memory area
Number of data
transfer words
CPU data transfer
area type
Name
0 to 15
0 to 15
Bit
13
Data read
Bit name
8-3 Data Read with Data Transfer Bit
Reading data starts the moment the bit turns
ON.
Set the number of words which you use for
writing/reading data.
Set the area type on the CPU side.
00B0 (hex): I/O Memory area (CIO)
00B1 (hex): Internal Auxiliary Memory area
(WR)
00B2 (hex): Holding Memory area (HR)
0082 (hex): DM area (DM)
0050 to 0068 (hex): EM Area (EM) in CJ2 CPU
Units*1
0050 (hex): EM bank No. 0
0051 (hex): EM bank No. 1
0068 (hex): EM bank No. 18
00A0 to 00AF (hex): EM Area (EM) in CJ1 CPU
Units*1
00A0 (hex): EM bank No. 0 (hex)
00A1 (hex): EM bank No. 1 (hex)
00AF (hex): EM bank No. F (hex)
*1. The number of available banks varies
depending on the CPU.
:
:
Function
8-26