FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 192

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
5.7.3
FX Series Programmable Controlers
ABSD (FNC 62)
Points to note:
a) The current value of the selected counter (S2) is compared against a user defined data
b) For each destination bit (D) there are two consecutive values stored in the data table. The
c) The data table has a length equal to 2
d) Values from 0 to 32,767 may be used in the data table.
e) The ABSD instruction may only be used ONCE.
From the example instruction and the data table below, the following timing diagram for
elements M0 to M3 can be constructed.
ABSD
FNC 62
(Absolute
drum
sequencer)
turned ON
D302 - 100
D304 - 160
D306 - 240
When counter S2 equals the
value below, the destination
D300 - 40
Mnemonic
table. This data table has a head address identified by operand S1. S1should always have
an even device number.
first allocated value represents the event number when the destination device (D) will be
turned ON. The second identifies the reset event. The data table values are allocated as a
consecutive pair for each sequential element between D and D+n.
table, a single entry can be one data word such as D300 or a group of 16 bit devices e.g.
K4X000.
device D is
turned OFF
D301 - 140
D303 - 200
D307 - 280
D305 - 60
Generates
multiple output
patterns in
response to
counter data
Function
destination
Assigned
device D
M0
M1
M2
M3
KnX, KnY,
KnM, KnS,
(in groups
of 8)
T, C, D
Note: High speed
counters are not
allowed
S
1
n data entries. Depending on the format of the data
Operation:
This instruction generates a variety of output
patterns (there are n number of addressed
outputs) in response to the current value of a
selected counter, S2.
C
S
Operands
2
Y,M,S
Note:
n
consecutive
devices are
used
D
Note:
n 64
K,H
n
Applied Instructions 5
ABSD:
9 steps
DABSD:
17 steps.
see f).
Program steps
5-70