AD5755-1x AD [Analog Devices], AD5755-1x Datasheet - Page 26

no-image

AD5755-1x

Manufacturer Part Number
AD5755-1x
Description
Quad Channel, 16-Bit, Serial Input, 4-20mA & Voltage Output DAC, Dynamic Power Control, HART Connectivity
Manufacturer
AD [Analog Devices]
Datasheet
AD5755-1
STATUS REGISTER
The Status Register is a read only register. This register contains any fault information as a well as a RAMP ACTIVE bit and a User Toggle
Bit. By setting the STATREAD bit in the Main Control Register, the Status Register contents can be readback on the SDO pin during every
write sequence.
Table 30. Decoding the Status Register
MSB
Table 31. Status Register Options
Option
OPEN CCT IA
OPEN CCT IB
OPEN CCT IC
OPEN CCT ID
SHORT CCT VA
SHORT CCT VB
SHORT CCT VC
SHORT CCT VD
RAMP ACTIVE
OVER TEMP
PEC ERROR
DC-DC A
DC-DCB
DC-DCC
DC-DCD
User Toggle Bit
D15
D12
to
X
DC
D15
DC-
D
DC
D14
DC-
C
D13
DC
DC-
Description
This bit will be set if a fault is detected on DACA I
This bit will be set if a fault is detected on DACB I
This bit will be set if a fault is detected on DACC I
This bit will be set if a fault is detected on DACD I
This bit will be set if a fault is detected on DACA V
This bit will be set if a fault is detected on DACB V
This bit will be set if a fault is detected on DACC V
This bit will be set if a fault is detected on DACD V
This bit will be set while any one of the output channels are slewing (slew rate control enabled on at least one
channel)
This bit will be set if the AD5755-1 core temperature exceeds approx. 150°C.
Denotes a PEC Error on the SPI Interface Transmit.
DC-DC Failure on Channel A. This fault indicates that the DCDC is not operating, for example if the boost inductor is
not connected.
DC-DC Failure on Channel B. This fault indicates that the DCDC is not operating, for example if the boost inductor is
not connected.
DC-DC Failure on Channel C. This fault indicates that the DCDC is not operating, for example if the boost inductor is
not connected.
DC-DC Failure on Channel D. This fault indicates that the DCDC is not operating, for example if the boost inductor is
not connected.
User Writable bit that the user can set and readback while doing a Status Register read. This can be used to verify
data communications if needed.
B
DC
D12
DC-
A
Toggle
User
D11
Bit
ERROR
D10
PEC
RAMP
ACTIVE
D9
Rev. PrD | Page 26 of 34
OVER
TEMP
D8
OUT
OUT
OUT
SHORT
CCT
VD
OUT
OUT
OUT
OUT
OUT
D7
pin.
pin.
pin.
pin.
pin.
pin.
pin.
pin.
SHORT
CCT VC
D6
SHORT
CCT VB
D5
Preliminary Technical Data
SHORT
CCT
VA
D4
OPEN
CCT
D3
ID
OPEN
CCT
D2
IC
OPEN
CCT
D1
IB
LSB
OPEN
CCT
D0
IA

Related parts for AD5755-1x