XW2Z-200J-B1 Omron, XW2Z-200J-B1 Datasheet - Page 200

no-image

XW2Z-200J-B1

Manufacturer Part Number
XW2Z-200J-B1
Description
CONNECTOR CABLE 2M
Manufacturer
Omron
Datasheet

Specifications of XW2Z-200J-B1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
XW2Z200JB1
One-shot Pulse Output Specifications
Pulse Outputs
Note
Set the pulse output operation mode to 1 shot in advance in the System
Setup, as shown in the following table.
A pulse output port that is being used for one-shot pulse outputs cannot be
used for any other pulse output functions.
The elapsed time of the one-shot pulse output is stored in 8-digit hexadecimal
in words A621 and A620 (pulse output 1) or A623 and A622 (pulse output 2).
When the one-shot pulse output is turned ON, the content of the correspond-
ing words is set to 0000 0000 hex and the content is incremented as time
passes. The final value is retained when the one-shot output is turned OFF.
One-shot pulse output
Pulse Output
A620
A621
A622
A623
Pulse ON time
Operating conditions 1. Set the pulse output operation mode to 1 shot in the System
Response time
Word
Tab page
Item
00 to 15
00 to 15
00 to 15
00 to 15
Bits
Pulse Output 1 − Operation mode
Pulse Output 2 − Operation mode
Elapsed time
of One-shot
pulse output 1
Elapsed time
of One-shot
pulse output 2
OFF
ON
Function
0.01 to 9,999 ms (Can be set with the STIM(980) instruction.)
2. Execute the STIM(980) instruction with operand C1 = #0001
Response time when the STIM(980) instruction is executed at
the beginning of an interrupt task:
0.2 ms max. from the generation of the interrupt until the
one-shot pulse output goes ON
Turned ON by STIM
instruction execution.
Setup.
or #0002.
Function
Setting units: Select 0.01 ms, 0.1 ms, or 1 ms.
Setting range: 0001 to 270F Hex (1 to 9,999)
Lower
4 digits
Upper
4 digits
Lower
4 digits
Upper
4 digits
Contains the elapsed time of the
one-shot pulse output in 8-digit hexa-
decimal.
The content can range from 0000 0000
to 0000 270F hex, and the units are set
to 0.01 ms, 0.1 ms, or 1 ms with the
STIM(980) instruction.
Note These words are refreshed dur-
These words function just like the
words for pulse output 1, described
above.
Specification
Turned OFF by hardware.
ing the Motion Control Module’s
I/O refreshing.
1 shot (one-shot pulse output)
1 shot (one-shot pulse output)
Contents
Setting
Section 7-6