Pulse Inputs
7-5-9
High-speed Counter Procedure
160
Pulse Input Function Procedures
1,2,3...
1. Determine the Input Mode, reset method, and Numeric Range.
2. Wire the input.
3. Make the necessary System Setup settings.
4. If the count check is being used, determine the count check (comparison)
5. Create the necessary ladder programming.
• Counting Speed: 50 kHz or 500 kHz
• Input Mode: Phase Differential, Increment/Decrement, or Pulse + Direc-
• Reset method: Phase Z and software reset, or Software reset
• Counter Operation: Circular Counter or Linear Counter
• Counting Speed: 50 kHz or 500 kHz
• Input Mode: Phase Differential, Increment/Decrement, or Pulse + Direc-
• Reset: Phase Z and software reset, or Software reset
• Counter Operation: Circular Counter or Linear Counter
• Count Check Method: Target-value Comparison or Range Comparison
• Turn ON the High-speed Counter 1 or 2 Start Bit (A610.00 or A611.00)
• CTBL(882) instruction: Specifies the port, registers the comparison table,
• INI(880) instruction: Specifies the port, changes the PV, and starts com-
• PRV(881) instruction: Specifies the port and reads the high-speed
tion
tion
method.
and start the high-speed counter.
and starts comparison.
parison.
counter PV.
Section 7-5