INT-1532L-5-M-000 TE Connectivity, INT-1532L-5-M-000 Datasheet - Page 40

DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V

INT-1532L-5-M-000

Manufacturer Part Number
INT-1532L-5-M-000
Description
DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V
Manufacturer
TE Connectivity
Datasheet

Specifications of INT-1532L-5-M-000

No. Of Digits / Alpha
4
Meter Function
Digital
Meter Range
0mA To 20mA
Digit Height
96mm
Supply Voltage Range
57.7V To 139V / 100V To 240V
Power Consumption
3W
Rohs Compliant
NA
Programmable Parameters
Programmable Display Unit Option
As an alternative to the standard software configuration package, voltage and current
transformer ratios, communication options and power measurement parameters can be
configured via the optional menu driven Integra display unit.
A simple two-button interface on the front panel of the unit allows display of 32 major
electrical and power quality parameters. To prevent unauthorised access to the product
settings, all screens can be protected by an optional customer programmable password.
Once configured, the status of each parameter can be viewed by scrolling through 13
screens, featuring a 3-line, 4-digit LED display. The unit requires an independent auxiliary
power supply and thus may be positioned either locally, or remotely from the transducer
at a distance limited only by the communication restrictions of RS485.
Specifications
Parameter
Password:
Primary current:
VT primary:
Secondary voltage:
Demand integration time:
Reset:
Pulse output duration:
Pulse rate divisors:
RS485 interface baud rate:
RS485 parity:
Modbus address:
Analogue outputs:
Input
Nominal input voltage:
Max continuous input voltage:
Max short duration input voltage: 2 x for 1 second, repeated 10 times at 10
System VT ratios (primary):
Nominal input voltage burden:
Nominal input current:
System CT primary values:
Max continuous input current:
Max short duration current input: 20 x for 1 second, repeated 5 times at
Nominal input current burden:
Outputs
RS485 communications:
Baud rates:
Pulsed:
Pulse duration:
Pulsed outputs:
Analogue outputs:
Range
4-digit 0000-9999
Max 9999A (360MW max**)
400kV (360MW max**)
Nominal system voltage
** maximum VT or CT ratios are limited so that
the combination of primary voltage and current
do not exceed 360MW at 120% of relevant input
8, 15, 20, 30 and 60 minutes
Max demand & active energy registers
60, 100, 200 milliseconds
1, 10, 100, 1000
2.4, 4.8, 9.6, 19.2 kB
Odd / even / no, 1 or 2 stop bits
1-247
User definable parameters & ranges
57.7 to 277V L-N, 100 to 480V L-L
120% nominal
second intervals
Any value up to 400kV **
< 0.2VA
5A (1A option)
9999:5A or 9999:1A max 360MW **
120% nominal
5 second intervals
< 0.6VA
** maximum VT or CT ratios are limited so that
the combination of primary voltage and current
does not exceed 360MW at 120% of relevant
input
2-wire half duplex
2400, 4800, 9600, 19200
Clean contact SPNO
60, 100 or 200 milliseconds
Up to 6
Up to 4
Continued
Measurement and Display
Up to 32 electrical and power quality
measurements can be configured and
monitored on the DIS-1540 optional
display unit. The displayed parameters
appear in the following order.
1
2
3
4
5
6
7
8
9
10 kWh (7-digit resolution)
11 kVArh (7-digit resolution)
12 kW demand
13 kW maximum demand
System volts
System current
System kW
System volts THD %
System current THD %
Volts L1–N (4-wire only)
Volts L2–N (4-wire only)
Volts L3–N (4-wire only)
Volts L1–L2
Volts L2–L3
Volts L3–L1
Volts line 1 THD %
Volts line 2 THD %
Volts line 3 THD %
Current L1
Current L2
Current L3
Current line 1 THD %
Current line 2 THD %
Current line 3 THD %
Neutral current (4-wire only)
Frequency
Power factor
kVAr
kVA
kW
Current demand
Current maximum demand
39