INT-1532L-5-M-000 TE Connectivity, INT-1532L-5-M-000 Datasheet - Page 19

DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V

INT-1532L-5-M-000

Manufacturer Part Number
INT-1532L-5-M-000
Description
DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V
Manufacturer
TE Connectivity
Datasheet

Specifications of INT-1532L-5-M-000

No. Of Digits / Alpha
4
Meter Function
Digital
Meter Range
0mA To 20mA
Digit Height
96mm
Supply Voltage Range
57.7V To 139V / 100V To 240V
Power Consumption
3W
Rohs Compliant
NA
Dimensions
Wiring
Input connections are made directly to shrouded screw-clamp terminals. Terminals for
both current and voltage connections are sized to accept two #12 AWG (3mm
2
) solid or
stranded wires. Connections for digital interface, pulsed and analogue options are via
screw-clamp connectors. Connectors offer retained wire protection leaves suitable for
one #13 AWG (2.5mm
2
) solid or stranded wire.
3-phase 3-wire unbalanced load
3-phase 4-wire unbalanced load
-
+
-
+
Import and Export Connections
The connection diagrams shown assume an import power configuration, therefore
power factor is shown as import (IMP) and current will flow towards the load. If current
flows away from the load, in an export power situation, then the power factor
indication will change to export (EXP). As Integra 2000 serves the full four power factor
conditions separate export connections are not required.
Auxiliary Supply
The Integra 2000 should ideally be powered from a dedicated supply, either 100-250V
ac/dc or 12-48V. However the device may be powered the signal source, provided the
source remains within the working range of the chosen auxiliary supply.
Fusing
It is recommended that all voltage lines are fitted with 1 amp fuses.
Safety/Ground Connections
For safety reasons, CT secondary connections should be grounded in accordance with
local regulations.
18

Related parts for INT-1532L-5-M-000