Specifications of INT-1532L-5-M-000

No. Of Digits / Alpha
4
Meter Function
Digital
Meter Range
0mA To 20mA
Digit Height
96mm
Supply Voltage Range
57.7V To 139V / 100V To 240V
Power Consumption
3W
Rohs Compliant
NA
DIN Integra 1530 Series
Multi-function Integra 1530 digital metering systems provide high
accuracy <0.2% measurement, display and communication of all major
electrical and power quality parameters, including true rms system
values, power quality data and total harmonic distortion (THD)
measurement up to the 31st harmonic. To meet customer
requirements, the range comes in single-phase, single-phase 3-wire,
3-phase 3-or 4-wire, and 3-phase 4-wire with neutral CT configurations.
This DIN 96 panel mounted enclosure offers simple programming and
display of up to 34 power measurement parameters via a simple menu
driven user interface on the front panel. Integra 1530 provides optional
pulsed, analogue and digital communication outputs, allowing the
communication of enhanced status information of up to 50 measured
parameters into building management systems. Additionally, a simple
Windows-based software package is available to remotely configure,
monitor and communicate all 50 major electrical and power
quality parameters.
Operation
Integra 1530 offers uncomplicated operation and high accuracy <0.2% measurement
of three phase voltage, current, frequency, watts, VAr, VA, energy, power factor, and
total harmonic distortion measurement of both phase and system, current and voltage.
Usually 3-phase 4-wire system line-to-line voltage measurements are usually derived
from calculating the vector of line-to-neutral voltage measurements. However, Integra
1530 readings even under phase fault conditions by providing true measurement of
both line-to-neutral, and line-to-line measurements.
For individual power monitoring applications, the Integra 1530 offers simple
programming and display, via the menu driven interface. An optional Windows-based
software configuration package can be used for remote configuration and monitoring.
Up to 50 electrical and power quality variables can be communicated into building
management systems via pulsed, analogue or digital communication options.
Functionality is easily enhanced to meet new client expectations. Integra pre-calibrated
plug-in option cards allow cost effective upgrades with any combination of pulsed,
analogue and digital communication outputs. Cards slot simply into the back of the unit
and products do not need to be removed from the installation or recalibrated.
Accuracy
Integra 1530 digital metering systems utilise true rms measurement techniques up to
the 31st harmonic, providing <0.2% accuracy. The robust frequency detection method,
able to lock the fundamental frequency onto any phase, results in an exceptional
tolerance to high harmonic frequencies. High integrity measurements are possible
where the system approximates CT current in the absence of voltage signals.
System Input
Designed for all low, medium and high voltage switchgear and distribution systems,
the Integra 1530 offers programmable VT and CT ratio capability. Direct connection for
up to 480V ac with 5A CT inputs is standard, and 1A CT inputs available as an option.
Neutral CT Input Option
High harmonic environments can produce unexpected and dangerous neutral currents.
Traditional 3-phase systems are only able to calculate the vector of line-to-neutral
current measurements, which may not register the true reading. Integra 1530 offers a
3-phase 4-wire version with a neutral 4th CT, allowing true neutral current
measurement and protection in high harmonic environments.
Features
Measure and display up to 34
electrical and power parameters
Measure and communicate up to 50
electrical and power parameters
High-contrast red LED display
LED annunciators for each
measured parameter
THD measurement and power quality
data to 31st harmonic
True rms measurement
Pulsed, analogue and digital outputs
Modbus, Johnson Controls, Lonworks
and Profibus interface options
Fully programmable VT and CT ratios
Benefits
Replaces multiple single function
instruments
Pre-calibrated plug-in options
High accuracy <0.2%
Configurable via software package or
menu driven interface
Import and export monitoring
Neutral CT input option
True 3-and 4-wire measurement
Applications
Switchgear
Distribution systems
Control panels
Embedded generation
Energy management
Building management
Utility power monitoring
Process control
Motor monitoring
Compliant With
UL file no: E20300
UL 61010B-1
IEC 1010-1/BSEN 61010-1 CAT III
9

Related parts for INT-1532L-5-M-000