INT-1532L-5-M-000 TE Connectivity, INT-1532L-5-M-000 Datasheet - Page 39

DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V

INT-1532L-5-M-000

Manufacturer Part Number
INT-1532L-5-M-000
Description
DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V
Manufacturer
TE Connectivity
Datasheet

Specifications of INT-1532L-5-M-000

No. Of Digits / Alpha
4
Meter Function
Digital
Meter Range
0mA To 20mA
Digit Height
96mm
Supply Voltage Range
57.7V To 139V / 100V To 240V
Power Consumption
3W
Rohs Compliant
NA
Measurement and
Communication
Up to 50 electrical and power quality
parameters can be measured and
communicated into building
management systems or viewed
through the software configuration
package via a PC.
Volts L1-N, L2-N, L3-N
Volts L1-L2, L2-L3, L3-L1
System volts L-N (average)
System volts L-L (average)
Current line 1, 2 and 3
System current (average)
Current sum
Current demand
Current maximum demand
Neutral current
System frequency
Watts 1, 2 and 3
System watts (sum)
Watts demand (import)
Watts maximum demand (import)
Watt-hours (import)
VAr 1, 2 and 3
System VAr (sum)
VAr-hours (import)
VA 1, 2 and 3
System VA (sum)
Power factor 1, 2 and 3
System power factor (average)
Phase aangle 1, 2 and 3
System phase angle (average)
THD volts 1, 2 and 3
THD system volts (mean)
THD amps 1, 2 and 3
THD system amps (mean)
38
System Outputs
Pulsed Outputs
Integra transducers offer optional pulsed outputs enabling the retransmission of kWh
and kVArh time based parameters. Outputs are pulsed at a rate proportional to the
measured kWh active energy, with pulse width and rate easily programmable either
locally or remotely. Output relays have fully isolated volt free contacts, with connection
via screw-clamp terminals.
Analogue Outputs
Up to four analogue outputs may also be included, enabling onward transmission of
linear parameters using industry standard analogue signalling. Each analogue channel
can be assigned to one of 47 measured parameters with the output span fully
adjustable to suit customer requirements, and can be configured to operate in normal,
reverse, threshold or constant current modes. Analogue outputs share a common
return which is galvanically isolated from non-analogue output terminals.
Digital Communications
RS485 Modbus RTU
Integra 1560 and 1580 transducers offer up to two RS485 communication ports for
direct connection to SCADA systems using the Modbus RTU protocol, or optionally, a
single Johnson Controls Metasys NII protocol. Remote monitoring enables the user to
record the system parameters in real time, using high resolution numbers. The
Modbus protocol establishes the format for the master’s query by placing it into the
device address. The slave’s response is also constructed using the Modbus protocol; it
contains the fields confirming the action taken, the data to be returned, and an error-
checking field. The Modbus option includes function 8 subfunction 0, which provides
return query data diagnostic support, and the ability to change Modbus word order to
suit the user requirements.
Lonworks Interface
The Lonworks interface option is designed according to the LonMark Interoperability
Guidelines version 3.2. This ensures Integra transducers can be integrated into a single
control network without requiring custom node or network tool development.
Profibus
The Profibus interface option allows Integra 1560 and 1580 to communicate over a
Profibus-DP network as a slave device. Integra can automatically detect the master
baud rate and communicate at data rates up to 12Mbit over the optically isolated
RS485 port. Connection is made via a Profibus standard 9-way D type connector. The
interface supports standard DP protocol functionality, Class 1 and Class 2 services and
networks can be configured using the GSD file.
INT-SOFT Communication and Configuration Software
Configuration of up to 50 measured parameters, outputs, pulsed relays, current and
power demand are easily programmed through a Windows style user interface, which
can be installed on any PC running Windows 95, NT or 2000. Communication with the
tranducer is through a connection with a PC COM port via a RS485/RS232 converter.
Configuration software allows the user to load and save configurations to a PC hard
disk and to send and retrieve settings directly from the Integra 1530. Settings can also
be copied between individual Integra units.
Status information is usually communicated into a building management system, but
can also be monitored through the configuration software. The software inquiries the
selected transducer every few seconds to obtain data, which can be viewed on a
dedicated measurements page.

Related parts for INT-1532L-5-M-000