INT-1532L-5-M-000 TE Connectivity, INT-1532L-5-M-000 Datasheet - Page 11

DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V

INT-1532L-5-M-000

Manufacturer Part Number
INT-1532L-5-M-000
Description
DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V
Manufacturer
TE Connectivity
Datasheet

Specifications of INT-1532L-5-M-000

No. Of Digits / Alpha
4
Meter Function
Digital
Meter Range
0mA To 20mA
Digit Height
96mm
Supply Voltage Range
57.7V To 139V / 100V To 240V
Power Consumption
3W
Rohs Compliant
NA
System Outputs
Pulsed Outputs
Integra 1530 digital metering system provides optional single or dual-pulsed outputs
enabling the retransmission of kWh and kVArh time-based parameters. Outputs are
pulsed proportionally to the measured kWh active energy, with pulse width and rate
easily programmable either locally or remotely. Output relays have fully isolated volt-
free contacts, with screw-clamp connection terminals.
Analogue Outputs
Supplies up to two analogue outputs, enabling onward transmission of linear
parameters with industry standard analogue signals. Each analogue channel can be
assigned to one of 47 measured parameters with an output span fully adjustable to
customer requirements and can be configured to operate in normal, reverse, threshold
or constant current modes. Both analogue outputs share a common return which is
galvanically isolated from non-analogue output terminals.
Digital Communications
RS485 Modbus RTU
Integra 1530 digital metering systems offer a RS485 communication port for direct
connection to SCADA systems using Modbus RTU or Johnson Controls Metasys NII
protocols. Remote monitoring enables the user to record system parameters in real
time using high-resolution numbers. The Modbus protocol establishes the format for
the master’s query by placing it into the device address. The slave’s response is also
constructed using Modbus protocol; it contains the fields confirming the action taken,
the data to be returned, and an errorchecking field. The Modbus option includes
function 8 subfunction 0, which provides return query data diagnostic support, and the
ability to change Modbus word order to suit user requirements.
Lonworks Interface
The Lonworks interface option is designed according to the LonMark Interoperability
Guidelines version 3.2. This ensures Integra digital metering systems can be integrated
into a single control network without requiring custom node or network tool development.
Profibus
The Profibus interface option allows Integra 1530 to communicate over a Profibus-DP
network as a slave device. Integra can automatically detect the master’s baud rate and
communicates at data rates of up to 12Mbit via a Profibus standard 9-way D type
connector over the optically isolated RS485 port. The interface supports standard DP
protocol functionality, Class 1 and Class 2 services and networks can be configured
using the GSD file.
INT-SOFT Communication and Configuration Software
Configuration of system parameters, outputs, pulsed relays, current and power demand
are easily programmed through the INT-SOFT Windows style user interface, installable
on any PC running Windows 95, NT or 2000. Communication to Integra 1530 is made
with a Modbus connection to a PC COM port via a RS485/RS232 converter.
Configuration software allows the user to load and save configurations to a PC hard
disk and to send and retrieve settings directly from the Integra 1530. Settings can also
be copied between individual Integra units.
Status information is usually communicated into a building management system, but
can also be monitored through the configuration software. The software queries the
selected Integra 1530 every few seconds to obtain data, which can be viewed on a
dedicated measurements page.
For more detailed information, please refer to the INT-SOFT Communication and
Configuration Software section of this brochure.
10