Fieldbus Controller
Fieldbus Controller 750-841
1. To configure the I/O of the fieldbus node in WAGO-I/O-PRO, select the
2. Expand the branch 'Hardware configuration' and the sub-branch 'K-Bus'
3. Click the entry 'K-Bus' or an I/O module with the right mouse key to open a
4. If the K-Bus structure is empty or the entry 'K-Bus' has been selected, use
5. If an I/O module has been selected in the K-Bus structure, use the command
6. The corresponding commands are also accessible via the menu 'Insert' in
7. Both commands open the dialog box 'I/O-configuration'.
8. In this dialog box you can select a desired I/O module from the catalog and
9. To get more information about an I/O module, select the desired module
10. Accept changes in the node configuration and close the dialog box by
Attention
The number of modules that you add must agree with the physical hardware
present (except for supply modules, potential multiplication modules, and end
modules
Note
You will find the most current version of the data sheets in the internet under
www.wago.com.
Configuration with the WAGO-I/O-PRO CAA I/O-Configurator
Resources tab in the left window of the screen, then double click on PLC
configuration in the tree structure.
The I/O-Configurator is starting.
in the tree structure.
context menu to insert and append of I/O modules.
the command 'Append Subelement' to select the desired I/O module and
attach it to the end of the K-Bus structure. The command 'Insert Element' is
inactive in this case.
'Insert Element' to select the desired I/O module and insert it into the
structure above the selected position. The command 'Append Subelement'
is inactive in this case.
the menubar of the main window.
place it in the node configuration. Place all necessary I/O modules in the
node configuration until the configuration fits to the physical node.
Add a module to the tree structure for each module in your node that
supplies or expects data in bits or words.
either from the catalog or from the node configuration and press the 'Data
Sheet' button. The data sheet corresponding to the selected module will be
opened in a new window.
pressing the 'OK' button. The addresses in the PLC-configuration are
recalculated and the tree structure is refreshed afterwards.
).
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP