750-841 WAGO, 750-841 Datasheet - Page 70

no-image

750-841

Manufacturer Part Number
750-841
Description
CONTR.ETHERNET TCP/IP 10/100MBIT
Manufacturer
WAGO
Datasheet

Specifications of 750-841

Rohs Compliant
YES
No. Of Digital Inputs
10
No. Of Digital Outputs
10
62 •
Fieldbus Controller
Fieldbus Controller 750-841
Adding an offset of 0x0200 to the MODBUS output address lets you read
back output data.
Fig. 3.1-9: Data exchange between MODBUS/TCP master and I/O modules
Starting from address 0x1000 there are the register functions. The register
functions made available in the coupler, can be addressed by the MODBUS
master along with the implemented MODBUS function codes (read/write). To
this effect, the individual register address is entered in place of the address of
a module channel.
Note
For MODBUS mapping, all output data over 256 words resides in the
memory area 0x6000 to 0x62FC, and can be read back with an offset of
1000
More information
You can find a detailed description of the MODBUS addressing in the
chapter „MODBUS Register Mapping“.
0x00FF
0x0000
hex
Inputs
(0x1000) added onto the MODBUS address.
Programmable Fieldbus Controller
PII
MODBUS master
I/O modules
0x62FC
0x6000
(0x02FF)
(0x0200)
00x0FF
0x0000
PIO
Outputs
(0x72FC)
(0x7000)
0x62FC
0x6000
PII = Process Input
PIO = Process Output
WAGO-I/O-SYSTEM 750
Image
Image
ETHERNET TCP/IP
g015045e

Related parts for 750-841