- Current page: 121 of 288
- Download datasheet (4Mb)
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
Fault code 2: -not used-
Fault argument
11
12
13
14
-
Fault when reading out the time
from the RTC
Fault when writing the time in
the RTC
Error Clock-Interrupt
Maximum number of Gateway or
Mailbox I/O modules exceeded
Fault description
not used
Fieldbus Controller 750-841
Adjust the clock and keep upright
the supply voltage of the bus
coupler for at least 15 minutes for
loading of the Goldcaps.
Adjust the clock and keep upright
the supply voltage of the bus
coupler for at least 15 minutes for
loading of the Goldcaps.
Adjust the clock and keep upright
the supply voltage of the bus
coupler for at least 15 minutes for
loading of the Goldcaps.
Turn off the power supply of the
node, reduce number of Gateway
or Mailbox I/O modules and turn
the power supply on again.
Trouble shooting
-
Fieldbus Controller