750-841 WAGO, 750-841 Datasheet - Page 48

no-image

750-841

Manufacturer Part Number
750-841
Description
CONTR.ETHERNET TCP/IP 10/100MBIT
Manufacturer
WAGO
Datasheet

Specifications of 750-841

Rohs Compliant
YES
No. Of Digital Inputs
10
No. Of Digital Outputs
10
40 •
3 Fieldbus Controller
3.1 Fieldbus Controller 750-841
3.1.1 Description
Fieldbus Controller 750-841
Description
The WAGO 750-841 Programmable Fieldbus Controller (PFC) combines the
functionality of an ETHERNET fieldbus coupler with the functionality of a
Programmable Logic Controller (PLC). When the PFC is used as a PLC, all
or some of its I/O modules can be control locally with the use of WAGO-I/O-
PRO CAA. WAGO-I/O-PRO CAA is an IEC 61131-3 programming tool,
which based on the standard programming system CoDeSys (a product of the
company 3S) with specific addition of the target files for all WAGO
controllers, used to program and configure the 750-841 PFC. I/O modules
which are not controlled locally, can be controlled remotely through the
10/100 Mbps ETHERNET Fieldbus port.
When power is applied to the PFC, it automatically detects all I/O modules
connected to the controller and creates a local process image. This can be a
mixture of analog and digital modules. The process image is subdivided into
an input and an output data area.
The data of the analog modules is mapped first into the process image. The
modules are mapped in the order of their position after the controller. The
digital modules are grouped after the analog modules, in the form of words
(16 bits per word). When the number of digital I/O’s exceeds 16 bits, the
controller automatically starts another word.
The controller has 512 KB of program memory, 128 KB of data memory, and
24 KB of retained memory. The programmer has access to all fieldbus and
I/O data.
To be able to send/receive process data via ETHERNET, the controller
supports a series of network protocols. For the exchange of process data, the
MODBUS TCP (UDP) protocol and the Ethernet/IP protocol are available.
Both communication protocols can be used alternatively or parallel.
For this, the write authorization, that means the access by PLC,
MODBUS/TCP or EtherNet/IP on the I/O modules are specified in a xml-file.
The protocol HTTP, BootP, DHCP, DNS, SNTP, FTP, SNMP and SMTP are
provided for the management and diagnosis of the system.
The programmer has the option to use function modules for programming
clients and servers for all transport protocols (TCP, UDP, etc.) via a socket-
API.
Library functions are available to extend the range of programming functions.
The IEC 61131-3 library "SysLibRTC.lib" enables integration of a buffered
real time clock with date (1 second resolution), alarm function, and a timer. In
the event of a power failure, this clock is powered by an auxiliary supply.
The controller is based on a 32-bit CPU and is capable of multitasking (i.e.,
several programs can be run at the same time).
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP