750-841 WAGO, 750-841 Datasheet - Page 217

no-image

750-841

Manufacturer Part Number
750-841
Description
CONTR.ETHERNET TCP/IP 10/100MBIT
Manufacturer
WAGO
Datasheet

Specifications of 750-841

Rohs Compliant
YES
No. Of Digital Inputs
10
No. Of Digital Outputs
10
5.2 Process Data Architecture for MODBUS/TCP
5.2.1 Digital Input Modules
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
With some I/O modules, the structure of the process data is fieldbus specific.
In the case of a coupler/controller with MODBUS/TCP, the process image
uses a word structure (with word alignment). The internal mapping method for
data greater than one byte conforms to the Intel format.
The following section describes the process image for various
WAGO-I/O-SYSTEM 750 and 753 I/O modules when using a
coupler/controller with MODBUS/TCP.
For the PFC process image of the programmable fieldbus controller is the the
structure of the process data mapping identical.
Digital input modules supply one bit of data per channel to specify the signal
state for the corresponding channel. These bits are mapped into the Input
Process Image.
When analog input modules are also present in the node, the digital data is
always appended after the analog data in the Input Process Image, grouped
into bytes.
Some digital modules have an additional diagnostic bit per channel in the
Input Process Image. The diagnostic bit is used for detecting faults that occur
(e.g., wire breaks and/or short circuits).
1 Channel Digital Input Module with Diagnostics
750-435
Note
Depending on the specific position of an I/O module in the fieldbus node,
the process data of all previous byte or bit-oriented modules must be
taken into account to determine its location in the process data map.
Bit 7
Bit 6
Bit 5
Process Data Architecture for MODBUS/TCP
Bit 4
Input Process Image
Bit 3
Bit 2
Diagnostic bit
Bit 1
S 1
I/O Modules
Data bit
Bit 0