750-841 WAGO, 750-841 Datasheet - Page 142

no-image

750-841

Manufacturer Part Number
750-841
Description
CONTR.ETHERNET TCP/IP 10/100MBIT
Manufacturer
WAGO
Datasheet

Specifications of 750-841

Rohs Compliant
YES
No. Of Digital Inputs
10
No. Of Digital Outputs
10
134 •
Fieldbus Communication
ETHERNET
(4) Management, Diagnostic and Application Protocols:
Positioned above the TCP/IP stack or UDP/IP layer are correspondingly
implemented management, diagnostic and application protocols that provide
services that are appropriate for the application. For the management and
diagnostic, these are, for example, SMTP (Simple Mail Transport Protocol)
for e-mails, HTTP (Hypertext Transport Protocol) for www browsers and
some others.
In this example, the protocols MODBUS/TCP (UDP) and EtherNet/IP are
implemented for use in industrial data communication.
Here the MODBUS protocol is also positioned directly above TCP (UDP)/IP;
EtherNet/IP, on the other hand, basically consists of the protocol layers
Ethernet, TCP and IP with an encapsulation protocol positioned above it. This
serves as interface to CIP (Control and Information Protocol).
DeviceNet uses CIP in the same way as EtherNet/IP. Applications with
DeviceNet device profiles can therefore be very simply transferred to
EtherNet/IP.
The advantage of this protocol is in the efficiency of the transmitted
data and the resultant increase in processing speed.
Many programs use both protocols. Important status information is
sent via the reliable TCP connection, while the main stream of data
is sent via UDP.
(3)
(2)
(1)
(4)
(3)
(2)
(1)
...
...
(physical interface, CSMA/CD)
(physical interface, CSMA/CD)
TCP, UDP
TCP, UDP
Ethernet
Ethernet
(e.g. positioning controllers, semi-
(explicit messages, I/O messages)
CIP message routing, connection
CIP application objects library
CIP data management services
conductors, pneumatic valves)
IP
IP
Application device profiles
Encapsulation
management
protocol
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP

Related parts for 750-841