750-841 WAGO, 750-841 Datasheet - Page 76

no-image

750-841

Manufacturer Part Number
750-841
Description
CONTR.ETHERNET TCP/IP 10/100MBIT
Manufacturer
WAGO
Datasheet

Specifications of 750-841

Rohs Compliant
YES
No. Of Digital Inputs
10
No. Of Digital Outputs
10
68 •
3.1.7.1.2 Allocating the IP Address to the Fieldbus Node
3.1.7.1.3 Testing the Function of the Fieldbus Node
Fieldbus Controller
Fieldbus Controller 750-841
1. To test the controller’s newly assigned I/P address, start a DOS window by
2. In the DOS window, enter the command: "ping " followed by the PFC’s IP
The following describes how to allocate the IP address for a fieldbus node
using the WAGO Ethernet Settings by way of an example.
Fig. 3.1-11: Example for the Function test of a Fieldbus Node
3. When the Enter key has been pressed, your PC will receive a query from
Note
You can download a free copy of the WAGO Ethernet Settings" which you
can find on the „ELECTRONICC Tools and Docs“ CD ROM (Item-No.:
0888-0412-0001-0101) and on the WAGO Web pages under
www.wago.com, "Service
For a short description to this you can find the "Quick Start" for the
ETHERNET Fieldbus Controller 750-841. Please have a look on the WAGO
Web pages under www.wago.com, "Service
Documentation".
4. Start the programm "WAGO Ethernet Settings".
5. Chose the register "TCP/IP".
6. In order to give the address now, change the specified option for the
7. Enter the desired IP address and if necessary the address for the Subnet
8. Click on the button "Write", to write the address down on the controller.
address assignment.
By default, the address is assigned automaticly with the BootP Server.
Activate now the option "Using following address" by clicking on the
radio button before this option.
Mask and for the Gateway.
clicking on the Start menu item Programs/MS-DOS Prompt
address in the following format:
ping [space] XXX . XXX . XXX . XXX (=IP address).
Example: ping 10.1.254.202
the controller, which will then be displayed in the DOS window.
If the error message: "Timeout" appears, please compare your entries
again to the allocated IP address and check all connections. Verify that the
TXD/RXD LEDs flash when the ping command is issued.
Downloads
Software".
Downloads
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
P012910d