C500RM201 Omron, C500RM201 Datasheet - Page 98

no-image

C500RM201

Manufacturer Part Number
C500RM201
Description
WRITE MASTER
Manufacturer
Omron
Datasheet

Specifications of C500RM201

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Error Codes and Monitoring
90
25103
25506
To check for other errors, monitor 25100 and force-set the system. This
causes the next error word to be displayed.
To read the next error, reset the Error Check bit and then set it. If the leftmost
Master has an error, the following is displayed. Errors in the Slaves cannot
be read if there is an error in the Master.
This is an example program to stop PC operation if an error occurs in the
Remote Terminal allocated word 62 (word 30 under Master with word multi-
plier of 1). Operation can be restarted by first removing the cause of the er-
ror, then setting and resetting the Error Check bit until the contents of IR 251
goes to 0000, and finally clearing the error via the Programming Console.
Incremented one by the Error Check flag.
Indicates word setting of 31 (allocated
word 63) with word multiplier at 1.
ANDW(34)
FALS(07)
MOV(21)
DM 0000
DM 0000
DM 0000
DM 0000
CMP(20)
END(01)
#FFF0
#3020
251
01
Master number
25100
Remote I/O Error flag turns
ON when there is an error.
The first step is thus to move
IR 251 to DM 0000.
The next error is read and
its word number displayed.
If there is not another error,
all 0s will be displayed.
Bits 0 to 3 are masked.
Data from DM 0000 is
compared with #3020.
If data matches, there is an
error in the Unit allocated
word 62 and the CPU Unit
stops.
Section 7-2