Recovery in STOP Mode
I/O Table Creation Problems
Slave Unit Numbers with Multiple Terminators
Applicable Products
1, 2, 3...
1, 2, 3...
1, 2, 3...
Note
When an error occurs in STOP mode, operational recovery is achieved
through any one of the following steps after the cause of the error has been
removed.
1.
2.
3.
1.
2.
3.
It is sometimes not possible to enter the I/O table directly following changes
to the number of Masters or Slaves. If table creation is not immediately possi-
ble, use the procedure given below for your PC. Before proceeding, be sure
that you have not exceeded the maximum number of Units allowed in a Re-
mote I/O System or Subsystem.
Clear the table and then recreate it. For all others remove the Masters.
1.
2.
3.
4.
5.
6.
7.
A feature enabling Slave unit numbers to be obtained when more than one
terminator has been set has been added to the C500-RM201 and C200H-
RM201 Remote I/O Master Units. This feature is available for products
manufactured on or after June 3, 1999 (confirm using the lot number; see
note).
The date of manufacture can be confirmed using the lot number. The first two
digits on the left indicate the day (01 to 31), the third digit indicates the month
(1 to 9, X (October), Y (November), Z (December)), and the fourth digit indi-
cates the last digit of the year.
Example
Lot number 0369
Press the TEST switch on the Master.
Re-register the I/O table in PROGRAM mode.
Turn the power to the Rack to which the Master is mounted off and then
back on.
Turn the Master’s Restart Bit ON and then back OFF.
Turn the power to the Rack to which the Master is mounted off and then
back on.
Re-register the I/O table in PROGRAM mode.
Turn off power to the PC(s).
Remove all Masters from their Racks.
Turn on the power to the PC(s), and enter the I/O table in PROGRAM
mode.
Turn off the power to the PC(s), and mount all Masters.
Turn on the power to all Slaves.
Turn on the power to the PC(s).
Enter the I/O table.
Manufactured on June 3, 1999.
Section 7-7
97