C500RM201 Omron, C500RM201 Datasheet - Page 26

no-image

C500RM201

Manufacturer Part Number
C500RM201
Description
WRITE MASTER
Manufacturer
Omron
Datasheet

Specifications of C500RM201

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
C200H Systems
2-2
14
Mounting Locations
Special I/O Units
Transmission Time
Group A
High-Speed Counter Unit Multi-Point I/O
Position Control Unit
(C200H-NC111/112,
C200HW-NC113/213)
ASCII Unit
Analog I/O Units
4 total
C200H Systems
Note
Group B
---
8 total
When constructing a Remote I/O System from C200H Masters and Slaves,
up to 2 Masters, 5 Slaves (regardless of the number of Masters), and 32 Re-
mote Terminals can be included. Optical Masters and Slaves, if controlled by
the PC, must be included in these totals. Expansion I/O Racks can be con-
nected to Slave Racks, however this limits the number of Slaves which the
PC can control i.e., each such Expansion I/O Rack must be counted as a
Slave Rack. The basic rules for Remote I/O Systems apply, e.g., each Master
Subsystem must be connected in series with a Master on one end and a ter-
minator (either a Remote Terminal or Slave) on the other end.
Masters can be mounted to any slot on the C200H CPU Rack or Expansion
I/O Rack. Masters should not be mounted, however, to either of the rightmost
two slots of the CPU Rack, as this would prevent mounting devices directly to
the CPU Unit. I/O Blocks are mounted to the Remote Interface, just as in
Systems using C500-RM201 Masters (see 2-1 Basic System ). Masters
cannot be mounted to Slave Racks or to Expansion I/O Racks connected to
Slave Racks
The numbers of Special I/O Units that can be mounted to any one Slave
Rack are shown in the following table. These figures assume that Units are
used only from one of the three groups.
If Units from more than one group are used, the following equations must be
met:
3A + B + 2C + 6D
A + B + C + D
The total number of Special I/O Units that can be used on all Racks com-
bined is 10. If PC Link Units are also used in the PC System, they must also
be included in the total.
Transmission time will be decreased with the same number of Slaves if two
Masters are used rather than one. Refer to Section 6 I/O Response Times .
1. The only Units that can be mounted to Remote I/O Slave Racks are Basic
2. High-density I/O Units (Group 2) and B7A Interface Units (Group 2) cannot
3. A Remote I/O Master Unit cannot be used if the CPU Unit is the
4. High-density I/O Units mounted on a Remote I/O Slave Rack can be used
I/O Units and Special I/O Units.
be used on Remote I/O Slave Racks.
C200H-CPU02.
only if the Remote I/O Master Unit is the C200H-RM201.
8
12
Group C
Temperature Sensor
Voice Unit
---
6 total
Group D
Position Control Unit
(C200H-NC211, C200HW-
NC413)
Motion Control Unit (C200H-
MC221)
---
2 total
Section 2-2