C500LK009V1 Omron, C500LK009V1 Datasheet - Page 89

no-image

C500LK009V1

Manufacturer Part Number
C500LK009V1
Description
PC LINK UNIT
Manufacturer
Omron
Datasheet

Specifications of C500LK009V1

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Broadcasting Data
NETWORK READ/WRITE Instructions
6-2-2 Instruction Specifications
Data Transfer Area
IR and
SR
LR
HR
AR
T/C
DM
EM
Area
000 to 511 (SEND)
000 to 252, 256 to
511 (RECV)
00 to 63
00 to 99
00 to 27
000 to 511
0000 to 6655
0000 to 6143
C200HX/HG/HE
Note With C200HX/HG/HE PCs, two Communications Units can be connected but
000 to 511 (SEND)
000 to 252, 256 to
511 (RECV)
00 to 63
00 to 99
00 to 27
000 to 511
0000 to 6655
None
It is possible to transfer the same data to all nodes in a network simultaneously
by designating the destination node as 00. This transmission is called broad-
casting. No responses are returned to broadcasts. (Broadcasting cannot be per-
formed with the RECV(98) instruction.)
the bridge function and gateway function cannot be used.
The NETWORK READ/WRITE instructions (SEND(90)/RECV(98)) enable
data to be sent and received between nodes within a single network under
control of a user program. The user can specify that a receiving node send a
response to the sending node to acknowledge receipt of the data. The basic
specifications of these instructions are given in the following table.
The data transfer area, which is used for data transmission and reception using
the SEND and RECV instructions, varies with the PC.
Transmission format
Packet length
Data content
Response time-out
parameters
Number of retries
C200HS
Node 1
000 to 255 (SEND)
000 to 252 (RECV)
00 to 63
00 to 99
00 to 27
000 to 511
0000 to 1999 (SEND)
0000 to 0999 (RECV)
Broadcast data
C200HX/HG/HE
Node 2
C200H
1:1 data transfer
1:N data transmit only (broadcast mode; no response)
256 words max. (within the same memory area only)
When SEND(90) is executed, command/response data
for a data transmission request is transferred.
When RECV(98) is executed, command/response data
for a data reception request is transferred.
00:
FF:
01 to FE:
0 to 15
Node 3
2 seconds
Response time-out ignored.
user-definable
(in increments of 100 ms, 100 to 25,400 ms)
000 to 255 (SEND)
000 to 252 (RECV)
00 to 63
00 to 99
00 to 27
000 to 511
0000 to 4095
C1000H
CS, CVM1/CV
Node 4
000 to 255 (SEND)
000 to 252 (RECV)
00 to 63
00 to 99
00 to 27
000 to 511
0000 to 6655
Section 6-2
Node 5
C2000H
Unit: word
75

Related parts for C500LK009V1