C500LK009V1 Omron, C500LK009V1 Datasheet - Page 76
C500LK009V1
Manufacturer Part Number
C500LK009V1
Description
PC LINK UNIT
Manufacturer
Omron
Datasheet
1.C500LK009V1.pdf
(174 pages)
Specifications of C500LK009V1
Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
- Current page: 76 of 174
- Download datasheet (961Kb)
Data Link Status
5-9-1 Automatic Data Link Table Generation
5-9-2 Manual Data Link Table Generation
62
Note *The PC Mode and PC Fatal Error Flags are not valid when a communications
When data link tables are generated automatically, data link status is output to
SR 238 through SR 241 for the operating-level-0 data link. And to SR 242
through SR 245 for the operating-level-1 data link.
Each of the above sets of four bits contains the four flags indicating data link sta-
tus for a node, as shown below.
error has occurred.
Any of the above bits that are not used by the System (i.e., those bits assigned to
node numbers beyond the possible range) can be used for work bits.
When data link tables are generated manually, data link status is output to con-
secutive words starting with the beginning status word designated in the refresh
parameters. Data status is only available for the nodes designated in the refresh
parameters, i.e., the nodes from which link data is being received. In the follow-
ing table “m” is the beginning status word.
The actual link status table will be only as long as required to store the status of
each node for which there is a link (see Example , below. Each of the above sets
of four bits operates as shown below.
SR 238
SR 239
SR 240
SR 241
00, 04, 08, or 12
01, 05, 09, or 13
02, 06, 10, or 14
03, 07, 11, or 15
m
m+1
m+2
m+3
m+14
m+15
Level 0
Word
Bits
SR 242
SR 243
SR 244
SR 245
Link no. 1
Link no. 5
Link no. 9
Link no. 13
Link no. 57
Link no. 61
Level 1
PC Mode*
PC Fatal Error*
Communications
Error
Data Link Status
00 to 03
Flag
Node 1
Node 5
Node 9
Node 13
00 to 03
Link no. 2
Link no. 6
Link no. 10
Link no. 14
Link no. 58
Link no. 62
04 to 07
Turned ON to indicate the PC is in RUN or
MONITOR mode. OFF indicates
PROGRAM mode.
Turned ON to indicate the PC has stopped
because of a fatal error.
Turned ON to indicate that there is a
communications error (time out), that the
Unit is not part of the System, or that the
data link is not active.
Turned ON to indicate the node is part of
the data link. OFF indicates that the data
link tables of the start-up node do not
match, or no operation is possible because
the data link table has not been created.
Node 2
Node 6
Node 10
Node 14
04 to 07
Bits
Link no. 3
Link no. 7
Link no. 11
Link no. 15
Link no. 59
08 to 11
Bits
Function
Node 3
Node 7
Node 11
Node 15
08 to 11
Section 5-9
Link no. 4
Link no. 8
Link no. 12
Link no. 16
Link no. 60
12 to 15
Node 4
Node 8
Node 12
Node 16
12 to 15
Related parts for C500LK009V1
Image
Part Number
Description
Manufacturer
Datasheet
Request
R
Part Number:
Description:
PROGRAMMING CONSOLE ADAPTER
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
TEACH BOX I/F CBL FOR NC
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
G6S-2GLow Signal Relay
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Compact, Low-cost, SSR Switching 5 to 20 A
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet: