CV-mode Commands for PCs
Parameters
6-5-7 RUN
Command Block
Response Block
Parameters
6-5-8 STOP
Command Block
Response Block
94
Note If the mode is not specified, the PC will go to MONITOR mode.
Program no. (command and response): Set to 0000.
First word (command and response): The program area begins at 00000000.
The first word must be an even number and will be returned as is in the response.
No. of bytes (command and response): The number of bytes in an even num-
ber up to 0200 (512 decimal). Bit 15 must be ON (1) when data is written to the
last word in the program area.
In the response, the no. of bytes is the actual number of bytes read.
Data (command): The data to be written.
Changes the PC to MONITOR or RUN mode, enabling the PC to execute its pro-
gram.
Program no. (command): Set to 0000.
Mode (command): As follows:
Changes the PC to PROGRAM mode, stopping program execution.
Command
Command
Command
Command
04
04
04
04
code
code
code
code
0002:
0004:
01
01
02
02
Response
Response
Bits 0 to 7 (second byte)
Bits 8 to 15 (first byte)
Program
RUN mode
MONITOR mode
code
code
no.
Mode
Bit 15 OFF (0): Without last word data
Bit 15 ON (1): With last word data
Bits 0 to 14: No. of bytes written