Specifications of C500LK009V1

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Data Link Characteristics
Node #7 PC Cycle Time
Minimum Response Time
Input
Input ON delay
Program
Note Noise may increase I/O delays.
Communications
cycle time
Data link I/O response time
The cycle time of the PC at node #7 is 50 ms or 15 ms.
The following diagram illustrates the data flow that will produce the minimum
response time, i.e., the time required if all signals and data transmissions are
processed as soon as they occur.
The equation for minimum data link I/O response time is as follows:
Response time =
input ON delay (0 ms) + cycle time of PC at node #0 (20 ms)
+ communications cycle time (19 ms) × 2 + cycle time of PC at node #7 (50 ms)
+ output ON delay (0 ms)
= 108 ms
Input device
1 cycle
SYSMAC LINK Unit
transmission processing
Data link transmission
PC at node #1
Program
Output ON
delay
1 cycle
Output
Output device
PC at node #7
I/O refresh
Data exchange
Section 5-10