Network Troubleshooting
Node cannot join data link
126
LNK indicator is not lit and
ERC indicator lit
ERH indicator lit
INS indicator not lit
RUN indicator not lit
ERC indicator lit
ERH indicator lit
• Check whether the Unit is mounted in a permissible slot on the Rack.
• Check whether the Unit operates normally when mounted on another PC.
• If none of the actions above solve the problem, replace suspect SYSMAC
• Check the PC’s Communications Controller Error Flags. If ON, replace the
• Check whether node number is within the range of 1 to 62. If not, reset to a
• Check for duplicate node numbers. Make sure each node number is assigned
• Check whether the Unit is mounted to an incompatible model or version or PC.
• Check for CPU Unit error in the PC. Switch power off and turn on again. If prob-
• Check for EEPROM error.
• Check whether local node number is greater than the maximum node number
• Check whether the same node number has been assigned twice.
• In coaxial cable systems, check whether the Terminators are connected prop-
• Check whether all cables are connected properly.
• Check whether the cables transmit properly.
Node cannot be entered into the data link. Check indicators on the node
which you want to add to data link.
• Check whether power is being supplied to the PC at adequate voltage.
• Check whether mounting screws on Unit are tight.
• Check whether the Unit is mounted in a permissible slot on the Rack.
• Check whether the Unit operates normally when mounted on another PC.
• If none of the actions above solve the problem, replace suspect SYSMAC
• Check the PC’s Communications Controller Error Flags. If ON, replace the
• Check whether node number is within the range of 1 to 62. If not, reset to a
• Check for duplicate node numbers. Make sure each node number is assigned
• Check whether the Unit is mounted to an incompatible model or version or PC.
• Check for CPU Unit error in the PC. Switch power off and turn on again. If prob-
• Check for EEPROM error.
LINK Units.
SYSMAC LINK Unit.
unique node number from 1 to 62 (duplicate node numbers not permitted).
to only one unit.
Replace PC if necessary.
lem occurs again, replace PC.
setting. If it is, lower local node number or increase maximum node number.
erly.
LINK Units.
SYSMAC LINK Unit.
unique node number from 1 to 62 (duplicate node numbers not permitted).
to only one unit.
Replace PC if necessary.
lem occurs again, replace PC.