Setting the Local IP Address
Method 2: Setting the Address in the CPU Bus Unit's Allocated DM Area
With this method, an IP address is not set in the TCP/IP Configuration (left at
its default setting), and an IP address is set in the allocated DM Area words
(the IP Address Display/Setting Area in words m+98 and m+99).
The IP address can be written in the two IP Address Display/Setting Area
words using the CX-Programmer or the Programming Console. To enable the
new IP Address setting, the EtherNet/IP Unit or built-in EtherNet/IP port must
be restarted or the PLC’s power must be turned OFF and then ON again.
Beginning word m = D30000 + (100 x unit number)
The following table shows the various Unit Setup when only the IP Address
Display/Setting Area is set, and the other TCP/IP Configuration settings are
left at their default values.
Method 3: Setting the TCP/IP Configuration from the Network
Configurator
This method can be used to set IP addresses from the CX-Programmer.
For details, refer to 3-8 TCP/IP and Link Settings.
If the IP address is set in the TCP/IP Tab Page, that IP address setting will be
displayed in the IP Address Display/Setting Area (words m+98 and m+99) in
the DM Area words allocated to the Unit/port.
m+98
m+99
IP address
Subnet mask
Default gateway
Preferred DNS server
Alternate DNS server
Host name
Domain name
Baud rate
IP Address: (1)(2).(3)(4).(5)(6).(7)(8) (Hex)
15
Setting
14
(1)
(5)
13
12
IP address set in words m+98 and m+99 (IP Address Dis-
play/Setting Area) of the DM Area words allocated to the
EtherNet/IP Unit as a CPU Bus Unit
Determined by class of the IP address
None (IP routing disabled)
None
None
None
None
Auto-detect
11
10
(2)
(6)
9
8
Operating status
7
6
(3)
(7)
5
4
3
Section 3-7
2
(4)
(8)
1
51
0

Related parts for CJ1W-EIP21