Example of Programming
to Process Data
Ladder Programming with Tag Data Links
Programming for Revision 1 or Higher
The following type of programming can be used to process data only when the
data links are operating normally.
Interlocks (IL and ILC instructions) and jumps (JMP and JME instructions) can
also be used to process data only when the data links are operating normally
as shown below.
Node A Data Link
Normal Operation Flag
Node B Data Link
Normal Operation Flag
Node C Data Link
Normal Operation Flag
Tag Data Link
n+11 bit 01
Error output
Local node
Operating
10000
Additional part
Release Flag
n+10 bit 00
n+10 bit 00
Unit Error
Unit Error
Occurred
Occurred
Normal Operation
Normal Operation
Flag
Flag
ILC
ILC
ILC
IL
IL
IL
The parts of the ladder program
that use the data link area for
the relevant node are processed
only when the corresponding
Normal Operation Flag is ON.
Node A data processing
Node B data processing
Node C data processing
DIFU
DIFD
Local node
Error output
10000
10000
Section 6-3
185