Setting Tag Data Links
6-2-7
156
Creating Connections Using the Wizard
1,2,3...
Note
7. Select Exit from the File Menu. The EtherNet/IP Datalink Tool will be exited
8. Returning to the Network Configurator
You can use the Network Configurator's Wizard to easily create connections
between OMRON PLCs following the instructions provided by the Wizard.
Network Configurator version 3.10 or higher is required to use the Wizard.
The Wizard can be used only with the following OMRON EtherNet/IP devices.
Use the following procedure to create connections (i.e., data links) with the
Wizard.
1. Set tags and tag sets for all devices before starting the Wizard. Refer to 6-
2. For tag data links between OMRON PLCs, a connection is created in the
CJ1W-EIP21
CJ1W-EIP21(CJ2)
CJ2B-EIP21
CJ2M-EIP21
CS1W-EIP21
b. No Table Inconsistencies
The following message will be displayed. Click the OK Button.
and you’ll return to the Network Configurator.
Click the icon for each device and check the settings made with the Ether-
Net/IP Datalink Tool in the Edit Device Parameters Dialog Box.
2-4 Creating Tags and Tag Sets for the setting procedure.
PLC (i.e., the originator device) that receives data as input data.
First, select the registered device for which you want to create a connec-
tion in the Network Configuration Window of the Network Configurator, and
then select Device - Parameters - Wizard from the menus.
Device name
CJ1W-EIP21 mounted to CJ1 CPU Unit
CJ1W-EIP21 mounted to CJ2 CPU Unit
Built-in EtherNet/IP port in CJ2H CPU Unit
Built-in EtherNet/IP port in CJ2M CPU Unit
CJ1W-EIP21 mounted to CS1 CPU Unit
Remarks
Section 6-2