Setting Tag Data Links
166
2. Select Network - Connect.
3. Click the Setup Button in the Setup Interface Dialog Box. The Registration
The registration information details are as follows:
The following Setup Interface Dialog Box will be displayed.
of the connection Dialog Box will be displayed. Enter the network informa-
tion for the connection destination, and then click the Add Button to regis-
ter the settings.
a. Registration name
b. Host (PC) information
c. Remote Information - EtherNet/IP Unit
• Network address
• Node address
• Network address
Same number as the network address of the Ethernet Unit of the PLC
that will be the relay node.
Last value in the computer's IP address (e.g., 1 for 192.168.250.1)
Network address set in the routing tables
Enter any name.
Enter information for the computer that has the Network Configurator
installed.
Enter the information for the EtherNet/IP Unit of the PLC that will be
the relay node.