LZSA-1000-3 TDK Corporation, LZSA-1000-3 Datasheet - Page 4

PWR SUP 24V 1008W 42A

LZSA-1000-3

Manufacturer Part Number
LZSA-1000-3
Description
PWR SUP 24V 1008W 42A
Manufacturer
TDK Corporation
Series
LZSAr
Type
Industrialr
Datasheets

Specifications of LZSA-1000-3

Power Supply Type
Switching (Closed Frame)
Voltage - Output
24V
Number Of Outputs
1
Power (watts)
1000W
Applications
Commercial
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
24 VDC @ 42 A
Size / Dimension
10.5" L x 5.62" W x 4.75" H (266.7mm x 142.7mm x 120.7mm)
Power (watts) - Rated
1008W
Operating Temperature
-40°C ~ 71°C
Efficiency
84%
Approvals
CE, EN, UL
Line Regulation
0.1%
Load Regulation
0.1%
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
24V
Output Current
42A
Power Rating
1008W
Input Voltage
85V AC To 265V AC / 100V DC To 400V DC
Brand/series
LZSA Series
Configuration
Enclosed
Operation
Linear
Output
24 VDC @ 42 A
Power, Output
1008 W
Primary Type
AC-DC
Special Features
High Reliability, Parallelable, Remote Adjust, Remote On/Off, Remote Sense
Voltage, Input
85 to 265/100 to 400 VAC/VDC
Voltage, Output
24 VDC
Input Frequency
47 to 440Hz
Screening Level
Commercial
Operating Temperature Min Deg. C
-40C
Operating Temperature Max Deg. C
71C
Mounting Style
Desktop
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1455
LZSA10003

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
LZSA-1000-3
Manufacturer:
TDK
Quantity:
100
LZS-A A 1000-3 3 Power Supply
1 Safety and Recommended Practices
1.1 General Safety Instructions
This power supply is a switch mode power supply for use in applications meeting a Pollution Degree
2 environment. A suitable mechanical and fire enclosure must be provided by the end use equip-
ment for shock hazard protection, fire protection and protection from hazardous energy levels.
1. Do not install, test or operate this product near water, and do not spill any liquid on it.
2. Do not operate this product unless it is in a secure position.
3. This product must be installed and put into service by authorized competent personnel only
4. This product is designed for use within other equipment or enclosures which restrict access to
5. This product must be reliably earthed and professionally installed in accordance with the
6. The case is connected to the product’s PE connection with screws. Therefore, screws at the
7. The output power taken from the power supply must not exceed the rating stated on the power
8. Openings in the product case are designed for ventilation and must not be obstructed when
9. Never push objects of any kind into the product through openings in its case as this could
10. Use copper stranded wire only, 12 to 14 AWG rated at 105°C for the AC input. All strands
11. Properly torque AC input terminals to 9 in-lb.
12. An internal fuse protects the unit and must not be replaced by the user. In case of internal
13. The output of this power supply is hazardous and must not be user accessible in the end use
14. The unit contains components that require special disposal. Make sure that the unit is
1.2 Safety Agency Approvals
Regulatory agency compliance applies only for operating frequencies between 47-63Hz.
No safety agency approvals for 100-380 VDC operation.
This product is approved to UL 60950-1/CAN CSA C22.2 No. 60950-1-03, First Edition, UL
508, Seventeenth Edition, EN 60950-1:2001, IEC 60950-1:2001, FM.
The CE Marking, when applied to the product, indicates conformance to the
provisions of the following European Directives:
Page. 2
Revision H : December 2009
who are fully conversant with the hazards of AC line operated equipment and with the
particular dangers associated with switch mode power supplies.
authorized competent personnel only and must not be user accessible.
prevailing electrical wiring regulations and safety standards. The product's PE connection is via
the tapped standoff and screw on the front panel marked with IEC 60417-1 Symbol 5019.
case must not be removed or loosened.
supply label.
the product is installed and/or operated.
result in electric shock or fire hazard.
72/23/EEC
89/336/EEC
must be secured in the terminal block to avoid potential danger of short circuit.
equipment. The (+) or (-) output can be earthed. Use wire rated at 105°C
of the rated load.
defect, the unit must be returned to the manufacturer.
properly disposed of at the end of its service life.
HIGH VOLTAGE WARNING: Dangerous voltages are present within the power supply.
READ SAFETY INSTRUCTIONS carefully before working on the unit.
Low Voltage Directive as amended by 93/68/EEC
EMC Directive as amended by 92/31/EEC and 93/68/EEC
NO USER SERVICEABLE PARTS INSIDE.
and
sized for 150%