C200HW-PD025 Omron, C200HW-PD025 Datasheet - Page 27

no-image

C200HW-PD025

Manufacturer Part Number
C200HW-PD025
Description
Power Supply
Manufacturer
Omron
Datasheet

Specifications of C200HW-PD025

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Current Consumption for Power Supply Units
■ Checking Current Consumption and Power Consumption
After selecting a Power Supply Unit based on considerations such as the power supply voltage, calculate the current and power
requirements for each Rack.
Condition 1: Current Requirements
There are three voltage groups for internal power consumption: 5 V, 26 V, and 24 V.
Condition 2: Power Requirements
For each Rack, the upper limits are determined for the current and power that can be provided to the mounted Units. Design the system
so that the total current consumption for all the mounted Units does not exceed the maximum total power or the maximum current
supplied for the voltage groups shown in the following tables.
● CPU Racks and Expansion Racks
The maximum current and total power supplied for CPU Racks and Expansion Racks according to the Power Supply Unit model are
shown below.
Note 1:For CPU Racks, include the CPU Backplane and CPU Unit current and power consumption in the calculations.
Conditions 1 and 2 below must be satisfied.
Condition 1: Maximum Current
Condition 2: Maximum Power
■ Example: Calculating Total Current and Power Consumption
Example: When the Following Units are Mounted to a CS-series CPU Rack Using a CS1W-PA204S Power Supply Unit
Note: For details on Unit current consumption, refer to Ordering Information.
• Current consumption at 5 V (internal logic power supply)
• Current consumption at 26 V (relay driving power supply)
• Current consumption at 24 V (power supply output terminals) (C200HW-PA204S only)
C200HW-PA204C
C200HW-PA204
C200HW-PA204S
C200HW-PA204R
C200HW-PA209R
C200HW-PD024
C200HW-PD025
C200HW-PD106R
CS1D-PA207R
CS1D-PD024
CPU Backplanes
(8 slots)
CPU Unit
Input Unit
Output Unit
Special I/O Unit
CPU Bus Unit
Service power supply
Current consumption
Power consumption
Power Supply Units
(1) Total Unit current consumption at 5 V ≤ (A) value
(2) Total Unit current consumption at 26 V ≤ (B) value
(3) Current consumption for service power supply at 24 V ≤ (C) value (Only when using the service power supply from the
(1) x 5 V + (2) x 26 V + (3) x 24 V ≤ (D) value
2: For Expansion Racks, include the Expansion Backplanes current and power consumption in the calculations.
C200HW-PA204S.)
Type
(A) 5 V
CS1W-BC083
CS1H-CPU67H
CS1W-ID211
CS1W-ID291
CS1W-OC201
CS1W-NC213
CS1W-CLK23
4.6 A
4.6 A
4.6 A
4.6 A
4.6 A
5.3 A
4.3 A
9 A
6 A
7 A
Max. current supplied
Model
(B) 26 V
0.56 A
0.6 A
0.6 A
0.6 A
0.6 A
1.3 A
0.6 A
1.3 A
1.0 A
1.3 A
Result
Result
Total
Total
0.3 A used
(C) 24 V
Quantity
0.8 A
---
---
---
---
---
---
---
---
---
1
1
2
2
2
1
1
(D) Max. total
power supplied
0.11 A + 0.82 A + 0.10 A x 2 +
0.20 A x 2 + 0.10 A x 2 +
0.25 A + 0.33 A
30 W
30 W
30 W
30 W
45 W
30 W
40 W
30 W
35 W
28 W
2.31 A x 5 V=11.55 W
2.31 A (≤ 4.6 A)
Programmable Controllers SYSMAC
0.11 A
0.82 A
0.10 A
0.20 A
0.10 A
0.25 A
0.33 A
5 V
---
11.55 + 2.496 + 7.2 = 21.246W (≤ 30W)
0.096 A x 26 V=2.496 W
0.096 A (≤ 0.6 A)
Voltage group
0.048 A x 2
0.048 A
26 V
---
---
---
---
---
---
---
CS1G/H
0.3 A x 24 V=7.2 W
0.3 A (≤ 0.8 A)
0.3 A
0.3 A
24 V
---
---
---
---
---
---
---
15