CS1D-IC102D Omron, CS1D-IC102D Datasheet - Page 302

no-image

CS1D-IC102D

Manufacturer Part Number
CS1D-IC102D
Description
CS1D Dual IO Control Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-IC102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Data Link Area
Forcing Bit Status
DeviceNet Area
Initialization
IOM Hold Bit Operation
8-5
Data Link Area
1,2,3...
For details on word allocations, refer to the CS/CJ Series DeviceNet Unit
Operation Manual (W380).
Bits in the CS-series DeviceNet Area can be force-set and force-reset.
The contents of the DeviceNet Area will be cleared in the following cases:
1. The operating mode is changed between PROGRAM and RUN or MONI-
2. The PLC’s power supply is cycled and the IOM Hold Bit is OFF or not pro-
3. The DeviceNet Area is cleared from a Programming Device.
4. PLC operation is stopped when a fatal error other than an FALS(007) error
By default, the DeviceNet Area is cleared when power is interrupted or the
CPU Unit is restarted.
If the IOM Hold BIt (A50012) is ON, the contents of the DeviceNet Area won’t
be cleared when a fatal error occurs or the operating mode is changed from
PROGRAM mode to RUN or MONITOR mode or vice-versa.
If the IOM Hold BIt (A50012) is ON and the PLC Setup’s “IOM Hold Bit Status
at Startup” setting is set to protect the IOM Hold Bit, the contents of the
DeviceNet Area won’t be cleared when the PLC’s power supply is cycled.
Data Link Area addresses range from CIO 1000 to CIO 1199 (CIO
bits 100000 to 119915). Words in the Link Area are used for data links when
LR is set as the data link area for automatic allocation for Controller Link Net-
works. It is also used for PLC Links.
DeviceNet Slaves
• With user-set allocations, the user can allocate words to Slaves from the
following words.
CIO 0000 to CIO 0235, CIO 0300 to CIO 0511, CIO 1000 to CIO 1063
W000 to W511
H000 to H511
D00000 to D32767
E00000 to E32767 (banks 0 to C)
TOR mode and the IOM Hold Bit is OFF.
tected in the PLC Setup.
occurs. (The contents of the DeviceNet Area will be retained when
FALS(007) is executed.)
CPU Unit
With fixed allocations, words are assigned according to node numbers.
(If a Slave requires two or more words, it will occupy as many node
numbers as words required.)
CS-series DeviceNet Unit
(CS1W-DRM21-V1)
CS-series DeviceNet Area
Section 8-5
267