V020-E3-2 Omron, V020-E3-2 Datasheet - Page 45

no-image

V020-E3-2

Manufacturer Part Number
V020-E3-2
Description
Publications, Books
Manufacturer
Omron
Datasheet

Specifications of V020-E3-2

Lead Free Status / RoHS Status
na
2-2-3
Installation
Power Supply Connection
Reference: When using an NT20S-ST122-V1, the NT20S must be started up before the host.
Note:
Connect a 24 VDC power supply to the power input terminals.
S Check the wiring carefully before turning on the power.
S Do not connect an AC power supply to the power supply terminals.
S Use a DC power supply with low voltage fluctuation.
S If complying with EC directives (low voltage directives), use a power supply with
For details, refer to “Switching the Power ON/OFF When Using C200H Direct”
(page 62). When not using C200H direct communication, there are no restrictions
on the order in which power supplies are switched ON and OFF.
S Power supply
reinforced insulation.
The specifications of the power supply that can be connected are as follows.
Power supply voltage
Allowable power supply voltage
fluctuation range
Power supply capacity
Power Supply
Breaker
24 VDC
Item
©
24 VDC
¨
24 VDC
20.4 VDC to 26.4 VDC
(24 VDC --15%, +10%)
10 W or over
Value
Section 2-2
29

Related parts for V020-E3-2