V020-E3-2 Omron, V020-E3-2 Datasheet - Page 204

no-image

V020-E3-2

Manufacturer Part Number
V020-E3-2
Description
Publications, Books
Manufacturer
Omron
Datasheet

Specifications of V020-E3-2

Lead Free Status / RoHS Status
na
5-3-6
188
Lamps, Touch Switches, Numeral Setting
Notification of Numbers to the PC
Word
m+1
m+2
The following describes how the numerical data input at the NT20S by using the
numeral setting function is ascertained by the PC.
In order to determine when numerical data has been input at the NT20S, the nu-
meral setting strobe flag in the PT status notify area is used. In order to determine
the upgraded numeral memory table number, the “content upgrade memory table”
in the PT status notify area is used.
When numerical data is input at the NT20S, this is automatically notified to the PT
status notify area (PT → PC) allocated in the PC memory as follows.
When the PC reads the “content upgrade memory table” at the leading edge of the
numeral setting strobe flag, it determines the numeral memory table number in
which the numerical data that was changed at the NT20S is stored.
[“Content upgrade memory table” in the PT status notify area and PT status]
Data is written to the content upgrade memory table as three digits of BCD (binary
coded decimal) data.
When the numeral setting strobe flag bit has been notified to the PC it returns to the
OFF (0) status.
For details on the method for storing a number in the word allocated for the numer-
al memory table, see “Displaying the Contents of Allocated Words of Memory
Tables” (page 167).
15 14 13 12 11 10 9
Numeral memory table #: 000 to 127
15 14 13 12 11 10
--
Notification of upgrade:
Upgraded numeral table number: Stored in the “content upgrade memory
PT status
0
0
12345678
0
Numerl memory table # (BCD, 3 digits)
--
8
NT20S
0
7
6
9
0
0
5
Numeral memory table 1
8
0
4
12345678
3
Bit
PT status
Allocated word (numeral table 1)
12345678
2
0
1
PT status numeral setting strobe flag
turned ON (1)
table”
0 Bit
PC
PT status notify area
Currently displayed screen
Numeral setting strobe flag
Content upgrade memory table
Content upgrade
PT status
memory table
PT status
Start
Start + 1
Table No.
Numeral setting
strobe flag
Section 5-3

Related parts for V020-E3-2