AN14BN0A3E032 EATON CUTLER HAMMER, AN14BN0A3E032 Datasheet - Page 10

Controller Starter

AN14BN0A3E032

Manufacturer Part Number
AN14BN0A3E032
Description
Controller Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of AN14BN0A3E032

No. Of Phases
Three
Current Rating
18A
Operating Temperature Range
-20°C To +65°C
External Width
1.75"
Current Min (full Load)
6.4A
Supply Voltage Max
120V
External Depth
3.49"
Mounting Type
DIN Rail
March 2009
Product Description
Single-phase, full voltage magnetic starters connect the
motor directly across the line, allowing it to draw full inrush
current during start-up. These starters are most commonly
used for control of self-starting single-phase motors up to
15 horsepower at 230V. They consist of a 2-pole electromag-
netic contactor to make and break the motor power circuit
and an overload relay to provide running overload protec-
tion. Starters listed in the table include:
CA08102001E
Two-pole Freedom Series contactor with long life twin
break, silver cadmium oxide contacts. Generously sized
for low resistance and cool operation. Designed to 3 mil-
lion electrical operations at maximum hp and 30 million
mechanical operations to Size 0, 10 million operations to
Size 2 and 6 million operations to Size 3.
Three-pole Freedom Series overload with poles 2 and 3
wired in series for motor overload protection. This over-
load is ambient compensated, selectable Manual or Auto-
matic reset, interchangeable Class 10 or 20 heater packs,
1.0 or 1.15 service factor selectability, overload trip indica-
tion and electrically isolated NO-NC contacts (pull RESET
button to test).
Holding circuit NO auxiliary contact supplied as standard.
On Size 00, the contact occupies the 4th power pole position.
Sizes 0 – 3 have the NO auxiliary mounted on the right
side of the contactor.
Steel mounting plate as standard on all open type starters.
Wired for separate or common control.
NEMA Size 1 — Cat. No. BN16DN0AB
For more information visit: www.eaton.com
NEMA Contactors & Starters
Freedom
Starters — Single-Phase Non-reversing, Full Voltage, Bi-Metallic Overload
Wiring Diagrams
Figure 33-25. Typical Wiring Diagrams — Single-Phase Applications
(Factory Wired)
Product Selection
When Ordering Specify
Table 33-104. Type BN16 NEMA — Manual or Automatic Reset
Overload Relay
Note: Starter Catalog Numbers do not include heater packs. Select 1
carton of 3 heater packs. Heater pack selection, Pages 33-107 –
33-108.
NEMA
Size
00
0
1
1P
2
3
For separate 120V control circuit. For maximum hp at listed motor
voltages, use the rating of other starters of same size.
Catalog Number
Heater Pack Number (see selection table, Pages 33-107 –
33-108) or full load current.
Maximum Horsepower
Motor
Voltage
115
230
115
230
115
230
115
230
115
230
115
230
Separate Control
Remove Wire “C” if supplied and connect separate control
lines to the Number 1 Terminal on the remote pilot device
and to the Number 96 Terminal on the overload relay.
omit Connector “A”
When more than
and connect per
one pushbutton
station is used,
sketch at right.
Auto Reset OL Relays
Not for Use with
2 Wire Control
2/T1 4/T2
OL
1-Phase
15
1
M
1
1
2
2
3
3
5
3
7-1/2
7-1/2
1/3
L1
T1
1
2
Front View of Panel
Accessories . . . . . . . . . . . . . Pages 33-82 – 33-90
Discount Symbol . . . . . . . . . 1CD1
AC Lines
A1
1 Phase Motor
3/14
1
T2
4
T1
6/T3
START “A”
A2
STOP
Magnet
Coil Voltage
(60 Hz)
120
240
120
240
120
240
120
240
120
240
120
240
L2
3
T2
3 Wire Control
2/13
3/14
98
97
96
Reset
95
“C”
START
STOP
START
STOP
Open Type 2-Pole
Catalog
Number
BN16AN0AC
BN16AN0BC
BN16BN0AC
BN16BN0BC
BN16DN0AB
BN16DN0BB
BN16PN0AB
BN16PN0BB
BN16GN0AB
BN16GN0BB
BN16KN0A
BN16KN0B
3/14
2/13
1
3/14
2/13
1
Price
U.S. $
33-77
33

Related parts for AN14BN0A3E032