SCS120PW48 TDK Corporation, SCS120PW48 Datasheet - Page 20

POWER SUP 48V 2.5A 120W OUTPUT

SCS120PW48

Manufacturer Part Number
SCS120PW48
Description
POWER SUP 48V 2.5A 120W OUTPUT
Manufacturer
TDK Corporation
Series
SCS120PWr
Datasheets

Specifications of SCS120PW48

Voltage - Output
48V
Number Of Outputs
1
Power (watts)
120W
Applications
Commercial
Power Supply Type
Switching (Open Frame)
Voltage - Input
90 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 2.5A
Size / Dimension
5" L x 3" W x 1.27" H (127mm x 76.2mm x 32.3mm)
Power (watts) - Rated
120W
Operating Temperature
0°C ~ 40°C
Efficiency
85%
Approvals
CE, CSA, EN, UL
Line Regulation
±3%
Load Regulation
±3%
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
48V
Output Current
2.5A
Power Rating
120W
Input Voltage
90VAC To 264VAC
Supply Voltage Typ
115VAC / 230VAC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Other names
285-1969
F e a t u r e s a n d B e n e f i t s
Feature
S p e c i f i c a t i o n s
ITEMS
Input Voltage range
Inrush Current
Input Current (115/230VAC)
Leakage Current
Hold Up Time (Typ)
Temperature Coefficient
Voltage Accuracy
Adjustment Range
Minimum Load
Total Regulation
Ripple & Noise
Overcurrent Protection
Overvoltage Protection
Remote On/Off
Efficiency
Off load power draw
Operating Temperature
Storage Temperature
Humidity (non condensing)
Cooling
Withstand Voltage
Isolation Resistance
Vibration (non operating)
Shock
Safety Agency Approvals
Conducted & Radiated EMI
Immunity
MTBF
Weight (Typ)
Size (WxLxH)
Warranty
(1) Derate linearly to 90W convection rating from 90 to 100VAC input.
Industry standard footprint
Wide Range AC Input
Dual input fuses
3055 Del Sol Blvd • San Diego, CA 92154 • 1-800-LAMBDA-4
mm
µA
ms
yrs
°C
W
A
A
%
%
A
%
%
%
V
V
g
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Input to Ground 1.5kVAC, Input to Output 4kVAC, Output to Ground 500VDC for 1 min.
CSS150 Series
3 x 5" 150W AC-DC Medical Power Supplies
Unit on: Floating or low <1.2V, Unit off: Apply 5V with respect to 0V
<60A maximum at 264VAC input, 25°C ambient cold start
0 to +70°C derate linearly to 50% load from 50 to 70°C
>100M at 25C & 70%RH, Output to Ground 500VDC
19.6m/s
110 - 150% of nominal (Cycle input power to reset)
90 - 264VAC (47 - 400Hz)(1) or 120 - 180VDC
UL60601-1, EN60601-1, IEC60601-1,CE Mark
3 x 5 x 1.3" (including underside components)
Benefit
2
Medical
Gaming
Test and Measurement
K e y M a r k e t S e g m e n t s & A p p l i c a t i o n s
(10~55Hz:2G Constant, X,Y,Z 60min each.)
Availability to second source
Global Operation
Easier system compliance
Convection or forced air (2.5m/s)
Wide Range AC Input
Low profile, Industry Standard Footprint
Global Safety Agency Compliance
100,000 (MIL-217F-HDBK)
EN55011-B, FCC Class B
<250µA 264VAC 63Hz
16ms at 115VAC input
< 196.1 m/s
2% peak to peak
EN60601-1-2
-20 to +85°C
20 - 95% RH
110 - 150%
±0.05%/°C
89% typical
1.7 / 0.85
Two Years
CSS150
<0.5W
None
340g
±1%
±3%
±3%
2
(20G)
19