2726188 Phoenix Contact, 2726188 Datasheet - Page 63

no-image

2726188

Manufacturer Part Number
2726188
Description
INTERBUS Bus Coupler
Manufacturer
Phoenix Contact
Datasheet
Connector types
6452_en_02
A
B
6.2
The following connector types are available for the 24 V DC area:
Figure 6-3
A
B
C
D
Standard connector
The green standard connector is used for the connection of two signals in 4-wire
technology or 8 signals in 1-wire technology (e.g., digital I/O signals).
The black standard connector is used to supply the supply voltage. Some of the
adjacent contacts can be jumpered internally (see Figure 6-4 on page 6-4).
Shield connector for connecting one cable
Shield connector for connecting two cables
Green connectors B and C are used for signals connected using shielded cables
(e.g., analog I/O signals, high-frequency counter inputs, remote bus cable).
FE or shielding is connected via a shield connection clamp rather than via a terminal
point.
Extended double signal connector
The green double signal connector is used for the connection of four signals in
3-wire technology (e.g., digital I/O signals).
The black double signal connector is used to supply the supply voltage. Some of
the adjacent contacts can be jumpered internally (see Figure 6-4 on page 6-4).
Connectors for the 24 V DC area
Connector types for Inline terminals
C
D