K3HB-SSD 24VACVDC Omron, K3HB-SSD 24VACVDC Datasheet - Page 6

SENS LINEAR METER DC PROCES INPT

K3HB-SSD 24VACVDC

Manufacturer Part Number
K3HB-SSD 24VACVDC
Description
SENS LINEAR METER DC PROCES INPT
Manufacturer
Omron
Series
K3HBr
Type
Linear Sensor Meterr
Datasheets

Specifications of K3HB-SSD 24VACVDC

Measuring Range
0 ~ 20mA, 0 ~ 10V
Display Style
Green, Red Characters, Black Background
Display Type
LCD
Display Face Size
3.78" L x 1.89" W (96.0 x 48.0mm)
Display Digits
5
Display Digits - Height
0.193" (4.90mm), 0.559" (14.20mm)
Backlight
Green, Red
Mounting Type
Panel Mount
Termination
Screw Terminals
Voltage - Supply
24VAC/DC
Power Consumption
7W
Svhc
No SVHC (15-Dec-2010)
External Depth
95mm
External Length / Height
48mm
Ip/nema Rating
IP20
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Supply Voltage
RoHS Compliant
Approval Bodies
CE, CRUus, UL
Current Consumption
50mA
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With
High-speed, High-precision
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
K3HB-SSD24VACVDC
K3HBSSD24VACVDC
■ Characteristics
6
Display range
Sampling period
Comparative output response time DC input: 100 ms max.; AC input: 300 ms max.
Linear output response time
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Weight
Degree of
protection
Memory protection
Applicable standards
EMC
Process Indicator
Front panel
Rear case
Terminals
K3HB-X
− 19,999 to 99,999
20 ms (50 times/second)
DC input: 150 ms max.; AC input: 420 ms max.
20 M Ω min. (at 500 VDC)
2,300 VAC for 1 min between external terminals and case
100 to 240 VAC models:
24 VAC/VDC models:
Frequency: 10 to 55 Hz; Acceleration: 50 m/s
150 m/s
Approx. 300 g (Base Unit only)
Conforms to NEMA 4X for indoor use (equivalent to IP66)
IP20
IP00 + finger protection (VDE0106/100)
EEPROM (non-volatile memory)
Number of rewrites: 100,000
UL61010C-1, CSA C22.2 No. 1010.1 (evaluated by UL)
EN61010-1 (IEC61010-1): Pollution degree 2/Overvoltage category II
EN61326: 1997, A1: 1998, A2: 2001
EMI: EN61326+A1 industrial applications
Electromagnetic radiation interference
Terminal interference voltage
EMS: EN61326+A1 industrial applications
Electrostatic Discharge Immunity
Radiated Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
Conducted Disturbance Immunity
Voltage Dips and Interruptions Immunity
± 1,500 V at power supply terminals in normal or common mode
(waveform with 1-ns rising edge and pulse width of 1 µ s/100 ns)
(waveform with 1-ns rising edge and pulse width of 1 µ s/100 ns)
CISPR 11 Group 1, Class A: CISPRL16-1/-2
CISPR 11 Group 1, Class A: CISPRL16-1/-2
EN61000-4-2: 4 kV (contact), 8 kV (in air)
EN61000-4-3: 10 V/m 1 kHz sine wave amplitude modulation (80 MHz to 1 GHz)
EN61000-4-4: 2 kV (power line), 1 kV (I/O signal line)
EN61000-4-5: 1 kV with line (power line), 2 kV with ground (power line)
EN61000-4-6: 3 V (0.15 to 80 MHz)
EN61000-4-11: 0.5 cycle, 0 ° /180 °, 100% (rated voltage)
± 1,500 V at power supply terminals in normal or common mode
2
(100 m/s
2
for relay outputs) 3 times each in 3 axes, 6 directions
2
, 10 sweeps of 5 min each in X, Y, and Z directions