K3HB-SSD 24VACVDC Omron, K3HB-SSD 24VACVDC Datasheet - Page 4

SENS LINEAR METER DC PROCES INPT

K3HB-SSD 24VACVDC

Manufacturer Part Number
K3HB-SSD 24VACVDC
Description
SENS LINEAR METER DC PROCES INPT
Manufacturer
Omron
Series
K3HBr
Type
Linear Sensor Meterr
Datasheets

Specifications of K3HB-SSD 24VACVDC

Measuring Range
0 ~ 20mA, 0 ~ 10V
Display Style
Green, Red Characters, Black Background
Display Type
LCD
Display Face Size
3.78" L x 1.89" W (96.0 x 48.0mm)
Display Digits
5
Display Digits - Height
0.193" (4.90mm), 0.559" (14.20mm)
Backlight
Green, Red
Mounting Type
Panel Mount
Termination
Screw Terminals
Voltage - Supply
24VAC/DC
Power Consumption
7W
Svhc
No SVHC (15-Dec-2010)
External Depth
95mm
External Length / Height
48mm
Ip/nema Rating
IP20
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Supply Voltage
RoHS Compliant
Approval Bodies
CE, CRUus, UL
Current Consumption
50mA
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With
High-speed, High-precision
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
K3HB-SSD24VACVDC
K3HBSSD24VACVDC
A Process Indicator Ideal for Discriminating and
Displaying Measurements for Voltage/Current
Signals
• Easy recognition of judgement results using color display that can be
• Equipped with a position meter for monitoring operating status trends.
• External event input allows use in various measurement and discrimina-
• Series expanded to include DeviceNet models.
• Short body with depth of only 95 mm (from behind the front panel), or
• UL certification approval (Certification Mark License).
• CE Marking conformance by third party assessment body.
• Water-resistant enclosure conforms to NEMA 4X (equivalent to IP66).
• Capable of high-speed sampling at 50 times per second (20 ms)
• Easy-to-set two-point scaling allows conversion and display of any user-
Model Number Structure
■ Model Number Legend
Base Units and Optional Boards can be ordered individually or as sets.
Base Units
1. Input Sensor Codes
5. Supply Voltage
Optional Board
Sensor Power Supply/Output Boards
Relay/Transistor Output Boards
Event Input Boards
Note: 1. CPA can be combined with relay outputs only.
Accessories (Sold Separately)
K32-DICN: Special Cable (for event inputs, with 8-pin connector)
K32-BCD: Special BCD Output Cable
4
K3HB-X@
K33-@
K34-@
K35-@
switched between red and green.
tion applications.
97 mm for DeviceNet models.
set values.
Process Indicator
K3HB-X
VD: DC voltage input
AD: DC current input
VA: AC voltage input
AA: AC current input
100-240 VAC: 100 to 240 VAC
24 VAC/VDC: 24 VAC/VDC
2. Only one of the following can be used by each Digital Indicator:
Refer to Precautions on page 30.
2
3
4
RS-232C/RS-485 communications, a linear output, or DeviceNet communications.
1
Process Indicator
5
K3HB-X
Base Units with Optional Boards
2. Sensor Power Supply/Output Type Codes
3. Relay/Transistor Output Type Codes
4. Event input Type Codes
K3HB-X@-@@@
None: None
CPA: Relay output (PASS: SPDT) + Sensor power supply
L1A: Linear current output (DC0(4) − 20 mA) + Sensor power supply
L2A: Linear voltage output (DC0(1) − 5 V, 0 to 10 V) + Sensor power supply
A: Sensor power supply (12 VDC +/−10%, 80 mA)
FLK1A: Communications (RS-232C) + Sensor power supply
FLK3A: Communications (RS-485) + Sensor power supply
None: None
C1: Relay contact (H/L: SPDT each)
C2: Relay contact (HH/H/LL/L: SPST-NO each)
T1: Transistor (NPN open collector: HH/H/PASS/L/LL)
T2: Transistor (PNP open collector: HH/H/PASS/L/LL)
BCD: BCD output + transistor output (NPN open collector: HH/H/PASS/L/
DRT: DeviceNet (See note 2.)
None: None
1: 5 points (M3 terminal blocks) NPN open collector
2: 8 points (10-pin MIL connector) NPN open collector
3: 5 points (M3 terminal blocks) PNP open collector
4: 8 points (10-pin MIL connector) PNP open collector
LL)
(12 VDC +/−10%, 80 mA) (See note 1.)
(12 VDC +/−10%, 80 mA) (See note 2.)
(12 VDC +/−10%, 80 mA) (See note 2.)
(12 VDC +/−10%, 80 mA) (See note 2.)
(12 VDC +/−10%, 80 mA) (See note 2.)
1 2 3 4
5