CRT1-ID08SL Omron, CRT1-ID08SL Datasheet - Page 66

no-image

CRT1-ID08SL

Manufacturer Part Number
CRT1-ID08SL
Description
8 In NPN Cage Clamp
Manufacturer
Omron
Datasheet

Specifications of CRT1-ID08SL

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Communications Cable Wiring Examples
2-4
2-4-1
42
Open Connector
Communications Cable Wiring Examples
Round Cable I
BS+
BDH
BDL
BS−
Master Unit or
Repeater Unit
Open Connector
Commu-
nications
BS+
communications
power supply
The following wiring is required in a CompoNet Network.
The wiring method depends on the type of cable that is used.
Relay terminal block
Slave Units can also be connected in parallel using multidrop connections.
BDH
24-VDC
• Two communications signal lines (communications data): BDH (communi-
• Two communications power supply lines (power for communications and
• Connect the two communications signal lines in parallel between the Mas-
• Use Open Type Connectors (DCN4-TB4, for connecting Units) to connect
• To supply the communications power (24 VDC), connect the two commu-
• Power is not supplied to the Master Unit or Repeater Units.
• A Terminating Resistor (DRS1-T) must be connected at the end of the
cations data high) and BDL (communications data low)
internal Slave Unit circuits): BS+ (communications power supply plus
side) and BS− (communications power supply minus side)
ter Unit or Repeater Unit and multiple Slave Units.
Communications Cables to Master Units, Repeater Units, and Slave
Units.
nications power supply lines to each Slave Unit separately from the Com-
munications Cables.
network.
BDL
Two communications
signal lines
BS−
Slave Unit
Communications
BS+
communications
power supply
BDH
24-VDC
BDL
BS−
Slave Unit
Communications
BS+
communications
power supply
BDH
24-VDC
BDL
BS−
Slave Unit
Terminating Resistor
Section 2-4
(121 Ω)