CRT1-ID08SL Omron, CRT1-ID08SL Datasheet - Page 390

no-image

CRT1-ID08SL

Manufacturer Part Number
CRT1-ID08SL
Description
8 In NPN Cage Clamp
Manufacturer
Omron
Datasheet

Specifications of CRT1-ID08SL

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Temperature Input Units
Setting the 1/100 Display Mode
366
1,2,3...
Eight words are allocated in the Master Unit for the four inputs, as shown in
the following diagram.
1. Turn ON power supply to the Temperature Input Unit.
2. With the CX-Integrator, double-click the icon of the Temperature Input Unit
3. Click the General Tab and select Temperature Data1 (1/100) in the Default
• Example 1: 850.00°C
• Example 2: −200.00°C
First word + 0CH
First word + 1CH
First word + 2CH
First word + 3CH
First word + 4CH
First word + 5CH
First word + 6CH
First word + 7CH
850 × 100 = 85,000 converted to hexadecimal → 0001 4C08 hex
Rightmost data = 4C08 hex; Leftmost data = 0001 hex
−200 × 100 = −20,000 converted to hexadecimal → FFFF B1E0 hex
Rightmost data = B1E0 hex; Leftmost data = FFFF hex
to be set in the Network Configuration Window or right-click the icon and
select Parameter - Edit to open the Configuration Window.
Connection Path (In) Field.
15
14 13
Input CH0 Temperature conversion data (rightmost)
Input CH0 Temperature conversion data (leftmost)
Input CH1 Temperature conversion data (rightmost)
Input CH1 Temperature conversion data (leftmost)
Input CH2 Temperature conversion data (rightmost)
Input CH2 Temperature conversion data (leftmost)
Input CH3 Temperature conversion data (rightmost)
Input CH3 Temperature conversion data (leftmost)
12
11
10 9
8
7
6 5
4
3
2
Section 7-1
1
0